Electrical
specifications
The table below contains the electrical specifications.
Electrical data
Specification
RZQ71B7V3B
RZQ100B7V3B
RZQ125B7V3B
Unit
Name
V3
Phase
1~
Voltage
230V
Frequency
50 Hz
Wire connections for power supply
See installation manual 4PW16864-1
Wire connections for connection with indoor
See installation manual 4PW16864-1
Power supply intake
Outdoor unit only
Compressor
Starting method
Inverter driven
Fan motor
No. of motors x output
1 x 70 W
2 x 70 W
Unit combination
Power supply
Compressor
OFM
IFM
Indoor unit
Outdoor unit
Hz-Volts
Voltage range
MCA
TOCA
MFA
MSC
RLA
kW
FLA
kW
FLA
FCQ71B7V3B
RZQ71B7V3B
50-230
Max.50Hz-253V
Min.50Hz-207V
17.1
17.1
20
16.2
16.2
0.07
0.3
0.045
0.6
FCQ35B7V1x2
RZQ71B7V3B
50-230
17.7
17.7
20
16.2
16.2
0.07
0.3
0.045x2
0.6x2
FFQ35BV1Bx2
RZQ71B7V3B
50-230
17.7
17.7
20
16.2
16.2
0.07
0.3
0.055x2
0.6x2
FBQ71B7V3B
RZQ71B7V3B
50-230
17.4
17.4
20
16.2
16.2
0.07
0.3
0.125
0.9
FBQ35B7V1x2
RZQ71B7V3B
50-230
17.5
17.5
20
16.2
16.2
0.07
0.3
0.065x2
0.5x2
FHQ71BUV1B
RZQ71B7V3B
50-230
17.1
17.1
20
16.2
16.2
0.07
0.3
0.062
0.6
FHQ35BUV1Bx2
RZQ71B7V3B
50-230
17.7
17.7
20
16.2
16.2
0.07
0.3
0.062x2
0.6x2
FAQ71BUV1B
RZQ71B7V3B
50-230
16.8
16.8
20
16.2
16.2
0.07
0.3
0.043
0.3
FUQ71BUV1B
RZQ71B7V3B
50-230
17.2
17.2
20
16.2
16.2
0.07
0.3
0.045
0.7
FCQ100B7V3B
RZQ100B7V3B
50-230
Max.50Hz-253V
Min.50Hz-207V
21.0
21.0
30
19.4
19.4
0.07+0.07
0.3+0.3
0.090
1.0
FCQ50B7V1x2
RZQ100B7V3B
50-230
21.2
21.2
30
19.4
19.4
0.07+0.07
0.3+0.3
0.045x2
0.6x2
FCQ35B7V1x3
RZQ100B7V3B
50-230
21.8
21.8
30
19.4
19.4
0.07+0.07
0.3+0.3
0.045x3
0.6x3
FFQ50BV1Bx2
RZQ100B7V3B
50-230
21.4
21.4
30
19.4
19.4
0.07+0.07
0.3+0.3
0.055x2
0.7x2
FFQ35BV1Bx3
RZQ100B7V3B
50-230
21.8
21.8
30
19.4
19.4
0.07+0.07
0.3+0.3
0.055x3
0.6x3
FBQ100B7V3B
RZQ100B7V3B
50-230
21.0
21.0
30
19.4
19.4
0.07+0.07
0.3+0.3
0.135
1.0
FBQ50B7V1x2
RZQ100B7V3B
50-230
21.4
21.4
30
19.4
19.4
0.07+0.07
0.3+0.3
0.085x2
0.7x2
FBQ35B7V1x3
RZQ100B7V3B
50-230
21.5
21.5
30
19.4
19.4
0.07+0.07
0.3+0.3
0.065x3
0.5x3
FHQ100BUV1B
RZQ100B7V3B
50-230
20.7
20.7
30
19.4
19.4
0.07+0.07
0.3+0.3
0.130
0.7
FHQ50BUV1Bx2
RZQ100B7V3B
50-230
21.2
21.2
30
19.4
19.4
0.07+0.07
0.3+0.3
0.062x2
0.6x2
FHQ35BUV1Bx3
RZQ100B7V3B
50-230
21.8
21.8
30
19.4
19.4
0.07+0.07
0.3+0.3
0.062x3
0.6x3
FAQ100BUV1B
RZQ100B7V3B
50-230
20.4
20.4
30
19.4
19.4
0.07+0.07
0.3+0.3
0.049
0.4
FUQ100BUV1B
RZQ100B7V3B
50-230
21.1
21.1
30
19.4
19.4
0.07+0.07
0.3+0.3
0.090
1.1
RZQ - Final.book Page 45 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...