Specifications
ESIE04-01
1–48
Part 1 – System Outline
3
11
4
5
3.4
FFQ
Technical
specifications
The table below contains the technical specifications.
Electrical
specifications
The table below contains the electrical specifications.
Specification
FFQ35BV1B
FFQ50BV1B
FFQ60BV1B
Heat exchanger
Rows x stages x fin pitch
2x10x1.5
Face area
Tube type
HiXSS diam. 7
Fin type
Multi louver fin
Fan
Air flow rate cooling (high)
10.0 m³/min
12.0 m³/min
15.0 m³/min
Air flow rate cooling (low)
6.5 m³/min
8.0 m³/min
10.0 m³/min
Air flow rate heating (high)
10.0 m³/min
–
15.0 m³/min
Air flow rate heating (low)
6.5 m³/min
–
10.0 m³/min
Qty x model
1 x D16P52A23
Fan speed
2 steps
Fan type
Turbo fan
Refrigerant
Type
R410A
Safety and functional devices
Air filter
Temperature control
Microcomputer control
Insulation
Heat
Both liquid and gas pipes
Sound absorbing
Weight
Unit
17.5 kg
Gross
21 kg
Specification
FFQ35BV1B
FFQ50BV1B
FFQ60BV1B
Unit
Phase
1~
Voltage
230V
Frequency
50 Hz
Fan motor
Running current (cooling)
0.40 A
0.49 A
0.61 A
Running current (heating)
0.36 A
–
0.56 A
Power consumption (cooling)
84 W
97 W
120 W
Power consumption (heating)
76 W
–
111 W
No. of motors x output
1 x 55 W
RZQ - Final.book Page 48 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...