Part 1 – System Outline
3
11
4
5
Allowable pipe
length and heigth
difference
When re-using existing piping, refer to below table for allowable piping length and heigth difference
(figures in brackets are equivalent lengths).
Model RZQ-B7
Liquid pipe
size
71
100
125
Maximum allowable piping length (*)
Pair: L1
Twin and triple: L1 + L2
Double twin: L1 + L2 + L4
size-down
10 m (15 m)
standard
50 m (70 m)
50 m (70 m)
50 m (70 m)
size-up
25 m (35 m)
35 m (45 m)
35 m (45 m)
Maximum total one-way piping length
Twin: L1 + L2 + L3
––
50 m
50 m
50 m
Triple: L1 + L2 + L3 + L4
––
Double twin:
L1 + L2 + L3 + L4 + L5 + L6 + L7
––
Maximum branch piping length
Twin: L2
Double twin: L2 + L4
––
20 m
Maximum difference between branch lengths
Twin: L2 - L3
––
10 m
10 m
10 m
Triple: L2 - L4
––
Double twin: L2 - L3, L4 - L5,
L6 - L7, (L2 + L4) - (L3 + L7)
––
Maximum heigth between indoor and outdoor
All: H1
––
30 m
Maximum heigth between indoors
Twin, triple and double twin: H2
––
0.5 m
Chargeless length
All:
L1 + L2 + L3 + L4 + L5 + L6 + L7
size-down
10 m
standard
30 m
size-up
15 m
RZQ - Final.book Page 68 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...