ESIE04-01
Part 1 – System Outline
1–71
Part 1
4.9
Piping Components
Components
The table below contains the different components of the functional diagrams.
No.
Component
Function / remark
1a
Flare connection
See pipe connection diameter.
2a
Liquid stop valve
The liquid stop valve is used as shut-off valve in case of a pump-down.
2b
Liquid stop valve
with service port
3
Gas stop valve with
service port
The gas stop valve is used as shut-off valve in case of a pump-down.
4
Compressor
The compressor can restart after 3 min from last stop.
5a
Capillary tube
The capillary tube allows pressure equalization during a compressor OFF-cycle.
5b
The capillary tube expands the liquid to enable evaporation in the evaporator.
6
Electronic expan-
sion valve
The expansion valve expands the liquid to enable evaporation in the evaporator. The opening
degree is controlled to obtain the optimum discharge temperature.
7
Heat exchanger
The heat exchanger is of the multi louvre fin type. Hi-X -tubes and coated waffle louvre fins are
used.
8
Filter
The filter is used to collect impurities, which may enter the system during installation and is also
used to avoid blockage of the capillaries and other fine mechanical parts of the unit.
9
Liquid receiver
The liquid receiver is used to make sure only completely liquefied refrigerant is sent to the expan-
sion valve. It is also used as a container in which surplus refrigerant is stored.
10
Check valve with
service port
The check valve allows you to connect a gauge.
11
Low-pressure switch
The low-pressure switch stops the operation of the unit when the pressure becomes abnormally
low.
12
High-pressure
switch
The high-pressure switch stops the operation of the unit when the pressure becomes abnormally
high.
13
Propeller fan and fan
motor
The propeller fan creates air displacement across the heat exhanger.
14a
One-way valve
The one-way valve is used to force the refrigerant liquid to flow through the receiver and the
expansion valve in the same direction both in cooling and heating.
14b
The one-way valve is used to release overpressure in the liquid receiver during stand-still.
15
4-way valve
(reversing solenoid
valve)
The 4-way valve is used to select refrigerant flow in cooling or heating mode.
When the 4-way valve switches from ON to OFF, a timer starts counting up to 150 as soon as the
cooling or defrosting operation is stopped. This delay time is to eliminate the switching sound.
16
Muffler
The muffler is used to absorb the refrigerant noise from the compressor.
17
Solenoid valve
P
Y1S: Capacity control solenoid valve
P
Y3S: Liquid injection solenoid valve
P
SV: Solenoid valve (Purge liquid receiver)
18
Thermistor
P
R1T: Air thermistor
P
R2T: Coil thermistor
P
R3T: Discharge pipe thermistor
19
Branch pipe
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...