background image

6 Installation

Installer reference guide

22

RZQG71~Y1 + RZQSG100~Y1

Split system air conditioners

4P385522-1A – 2016.10

6.7.3

Precautions when connecting the
electrical wiring

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

CAUTION

For  use  of  units  in  applications  with  temperature  alarm
settings  it  is  recommended  to  foresee  a  delay  of  10
minutes  for  signalling  the  alarm  in  case  the  alarm
temperature  is  exceeded.  The  unit  may  stop  for  several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.

6.7.4

Guidelines when connecting the electrical
wiring

Keep the following in mind:

▪ If stranded conductor wires are being used, install a round crimp-

style  terminal  on  the  tip.  Place  the  round  crimp-style  terminal  on
the  wire  up  to  the  covered  part  and  fasten  the  terminal  with  the
appropriate tool.

b

a

a

Stranded conductor wire

b

Round crimp-style terminal

▪ Use the following methods for installing wires:

Wire type

Installation method

Single core wire

c b

c

a

a

A

AA´

a

 Curled single core wire

b

 Screw

c

 Flat washer

Stranded conductor
wire with round
crimp-style terminal

c b

b

a

c

a

B

B

a

 Terminal

b

 Screw

c

 Flat washer

Tightening torques

Item

Tightening torque (N•m)

M4 (X1M)

1.2~1.8

M4 (earth)

1.2~1.4

M5 (X1M)

2.0~3.0

M5 (earth)

2.4~2.9

6.7.5

Specifications of standard wiring components

Component

RZQG

RZQSG

V1

Y1

V1

Y1

71

100

125+140

71

100

125+140

100

125+140

100

125

140

Power supply cable MCA

(a)

20.6 A

32.0 A

33.5 A

14.0 A

21.0 A

22.5 A

32.0 A

33.5 A

17.7 A

19.2 A

22.5 A

Voltage

230 V

400 V

230 V

400 V

Phase

1~

3N~

1~

3N~

Frequency

50 Hz

Wire sizes

Must comply with applicable legislation

Interconnection cables

Minimum cable section of 2.5 mm² and applicable for 230 V

Recommended field fuse

25 A

40 A

16 A

25 A

40 A

20 A

25 A

Earth leakage circuit breaker

Must comply with applicable legislation

(a)

MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).

6.7.6

To connect the electrical wiring on the
outdoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

1

Remove  the  service  cover.  See 

"6.2.2  To  open  the  outdoor

unit" on page 12

.

2

Strip insulation (20 mm) from the wires.

a

b

a

Strip wire end to this point

b

Excessive strip length may cause electrical shock or
leakage.

3

Connect  the  interconnection  cables  and  power  supply  as
follows:

Summary of Contents for RZQG71L9V1B

Page 1: ...rs English Installer reference guide Split system air conditioners RZQG71L9V1B RZQG100L9V1B RZQG125L9V1B RZQG140L9V1B RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B RZQSG100L9V1B RZQSG125L9V1B RZQ...

Page 2: ...ng to the outdoor unit 16 6 4 9 To determine if oil traps are required 17 6 5 Checking the refrigerant piping 17 6 5 1 About checking the refrigerant piping 17 6 5 2 Precautions when checking the refr...

Page 3: ...F BURNING Do NOT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you...

Page 4: ...ion WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the...

Page 5: ...esistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do not connect wiring of different thicknesses to the...

Page 6: ...allation What to do and know to install the system Commissioning What to do and know to commission the system after it is installed Hand over to the user What to give and explain to the user Maintenan...

Page 7: ...L7 in combination with RZQG_V1 you also have to install the demand adaptor kit For installation instructions see the installation manual of the bottom plate heater Demand adaptor kit Can be used for t...

Page 8: ...eaker 1 5 height of outdoor unit Mind the service space requirements when installing the windbreaker a b c d c d a Sea wind b Building c Outdoor unit d Windbreaker Strong winds 18 km h blowing against...

Page 9: ...oil checking reference card This is available from your dealer 1 Put some residual oil from the piping on a piece of white paper 2 Compare the colours If the oil colour is Then Identical to or darker...

Page 10: ...iquid piping 9 5 mm Gas piping 15 9 mm L1 pair twin triple double twin Model New a Existing b L1 liquid piping L1 gas piping RZQG71 Size down 6 4 mm 12 7 mm Standard 9 5 mm 15 9 mm Size up 12 7 mm RZQ...

Page 11: ...m b 25 m 35 m b 3 Maximum allowable piping length Pair N A Twin L1 L2 L3 Limit 60 m 75 m 50 m Triple L1 L2 L3 L4 Limit 75 m 50 m Double twin L1 L2 L3 L4 L5 L6 L7 Limit 75 m 50 m 4 Maximum branch pipi...

Page 12: ...because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents WARNING All wiring must be performed by an authorized electrician and must co...

Page 13: ...0 350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundatio...

Page 14: ...ting the refrigerant piping to the indoor unit Installing oil traps Insulating the refrigerant piping Keeping in mind the guidelines for Pipe bending Flaring pipe ends Brazing Using the stop valves 6...

Page 15: ...stration A Flare tool for R410A clutch type Conventional flare tool Clutch type Ridgid type Wing nut type Imperial type A 0 0 5 mm 1 0 1 5 mm 1 5 2 0 mm 5 Check that the flaring is properly made a b c...

Page 16: ...tem cap is sealed where indicated with the arrow Do NOT damage it After handling the stop valve tighten the stem cap and check for refrigerant leaks Item Tightening torque N m Stem cap liquid side 13...

Page 17: ...is might cause liquid compression or deterioration of oil return Oil traps in the rising gas piping can prevent this If Then The indoor unit is installed higher than the outdoor unit Install an oil tr...

Page 18: ...be caused by e g the closed state of the expansion valve in the outdoor unit circuit but does NOT present any problem for correct operation of the unit 6 5 5 To perform vacuum drying 1 Vacuum the sys...

Page 19: ...nents with specific functions e g valves The refrigerant circuit therefore features additional service ports for vacuuming pressure relief or pressurizing the circuit In case it is required to perform...

Page 20: ...ize up G2 m Total length of 6 4 mm liquid piping 2 Determine R1 and R2 If Then G1 30 m a Use the table below to determine R1 length G1 30 m a and R2 length G2 If Then G1 30 m a and G1 G2 30 m a R1 0 0...

Page 21: ...see unit name plate c Additional refrigerant amount charged d Total refrigerant charge e Greenhouse gas emissions of the total refrigerant charge expressed as tonnes CO2 equivalent f GWP Global warmin...

Page 22: ...d conductor wire with round crimp style terminal c b b a c a B B a Terminal b Screw c Flat washer Tightening torques Item Tightening torque N m M4 X1M 1 2 1 8 M4 earth 1 2 1 4 M5 X1M 2 0 3 0 M5 earth...

Page 23: ...ies a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at th...

Page 24: ...rate the unit without thermistors and or pressure sensors switches Burning of the compressor might result NOTICE Do NOT operate the unit until the refrigerant piping is complete when operated this way...

Page 25: ...the unit to cooling operation mode 2 Start the test run Action Result 1 Go to the home menu Cool Set to 28 C 2 Press at least 4 seconds The Service Settings menu is displayed 3 Select Test Operation...

Page 26: ...he user what to do in relation to maintaining the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least onc...

Page 27: ...ANGER RISK OF EXPLOSION Pump down Refrigerant leakage If you want to pump down the system and there is a leakage in the refrigerant circuit Do NOT use the unit s automatic pump down function with whic...

Page 28: ...A B C D E HB HU HD B 100 A B C 100 100 100 B E 100 1000 500 A B C E 150 150 150 1000 500 D 500 D E 1000 500 500 500 500 B D 100 100 B D E HB HD HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500...

Page 29: ...red to install a roof but seal the gap between the upper and lower units to prevent discharged air from flowing back to the suction side through the bottom of the unit 12 2 Piping diagram Outdoor unit...

Page 30: ...1U F2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG100 140_V1 RZQSG125 140_V1 F1U F4U Fuse F6U Fuse T 5 0 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQ S G_Y1 F1U F2U Fuse 31...

Page 31: ...ed company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure...

Page 32: ...4P385522 1A 2016 10 Copyright 2014 Daikin...

Reviews: