11 Disposal
Installer reference guide
27
RZQG71~Y1 + RZQSG100~Y1
Split system air conditioners
4P385522-1A – 2016.10
DANGER: RISK OF ELECTROCUTION
WARNING
Prevent hazard due to the inadvertent resetting of the
thermal cut-out: this appliance must NOT be supplied
through an external switching device, such as a timer, or
connected to a circuit that is regularly turned ON and OFF
by the utility.
DANGER: RISK OF BURNING
11
Disposal
11.1
Overview: Disposal
Typical workflow
Disposing of the system typically consists of the following stages:
1
Pumping down the system.
2
Dismantling the system according to the applicable legislation.
3
Treating the refrigerant, oil and other parts according to the
applicable legislation.
INFORMATION
For more details, see the service manual.
11.2
About pump down
The unit is equipped with an automatic pump down function, with
which you can collect all refrigerant from the system into the outdoor
unit.
Example:
To protect the environment, pump down when relocating
the unit or when disposing of the unit.
NOTICE
The outdoor unit is equipped with a low pressure switch or
a low pressure sensor to protect the compressor by turning
it OFF. NEVER short-circuit the low pressure switch during
pump down operation.
11.3
To pump down
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage.
If you want to pump
down the system, and there is a leakage in the refrigerant
circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit.
Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
1
Turn ON the main power supply switch.
2
Make sure the liquid stop valve and the gas stop valve are
open.
3
Press the pump down button (BS4) for at least 8 seconds. BS4
is located on the PCB in the outdoor unit (see wiring diagram).
Result:
The compressor and outdoor unit fan start
automatically, and the indoor unit fan might start automatically.
4
±2 minutes after the compressor started, close the
liquid stop
valve
. If it is not closed properly during compressor operation,
the system cannot be pumped down.
5
Once the compressor stops (after 2~5 minutes), close the
gas
stop valve
.
Result:
The pump down operation is finished. The user
interface may display "
" and the indoor pump may continue
operating. This is NOT a malfunction. Even if you press the ON
button on the user interface, the unit will NOT start. To restart
the unit, turn OFF the main power supply switch and turn it ON
again.
6
Turn OFF the main power supply switch.
NOTICE
Make sure to reopen both stop valves before restarting the
unit.