Installation manual

6

Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to figures

2

3

4

 and 

5

. Assume that the longest line in the figure corresponds

with the actual longest pipe, and the highest unit in the figure
corresponds with the actual highest unit.

Allowable pipe length

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).

During tests never pressurize the appliances with a pressure
higher than the maximum allowable pressure (see unit name
plate: PS).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.

Great caution is needed when passing copper tubes through
walls.

In case of simultaneous operating system
-

Upward and downward piping should be performed at the 
main piping line.

-

Use branch piping kit (optional) for branching refrigerant 
pipes.

Precautions to be taken. (For details, refer to the manual attached to
branch piping kit.)

-

Install the branch pipes horizontally (with a maximum 
inclination of 15°) or vertically.

-

Length of branch pipe to the indoor unit should be as short as 
possible.

-

Try to keep lengths of both branch pipes to the indoor unit 
equal.

R

EFRIGERANT

 

PIPING

Field pipes can be installed in four directions.

Figure - 

Field pipes in four directions

Cutting out the two slits makes it possible to install as shown in
the 

figure "Field pipes in four directions"

.

(Use a metal saw to cut out the slits.)

To install the connecting pipe to the unit in a downward direction,
make a knockout hole by penetrating the centre area around the
knockout hole using a 

Ø

6 mm drill. (See 

figure "Field pipes in

four directions"

.)

After knocking out the knock-out, it is recommended to apply
repair paint to the edge and the surrounding end surfaces to
prevent rusting.

Allowable pipe length

Liquid pipe 

size

Model

71

100

125

140

Maximum total one-way piping length

Pair

L1

standard

30 m 

(40 m)

50 m (70 m)

• Twin and triple
• Double twin

• L1+L2
• L1+L2+

L4

standard

Maximum allowable piping length

(a)

(a) Parenthesized figure represents the equivalent length.

Twin

L1+L2+L3

30 m

50 m

50 m

Triple

L1+L2+L3+
L4

Double twin

L1+L2+L3+
L4+L5+L6+
L7

Maximum branch piping length

• Twin and triple
• Double twin

• L2
• L2+L4

20 m

Maximum difference between branch lengths

Twin

L2–L3

10 m

10 m

10 m

Triple

L2–L4

Double twin

• L2–L3
• L4–L5
• L6–L7
• (L2+L4)–

(L3+L7)

Maximum height between indoor and outdoor

All

H1

15 m

30 m

Maximum height between indoors

Twin, triple and 
double twin

H2

0.5 m

Chargeless length

All

L1+L2+L3+
L4+L5+L6+
L7

standard

30 m

Place

Installation period

Protection method

Outdoor unit

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor unit

Regardless of the 

period

1

Drill

8

Pipe outlet plate

2

Centre area around 
knockout hole

9

Screw front plate

10

Pipe outlet plate screw

3

Knockout hole

11

Forward

4

Slit

12

Backward

5

Connecting pipe

13

Sideways

6

Bottom frame

14

Downward

7

Front plate

4

4

3

2

1

7

8

9

10

11

14

13

12

5

6

Summary of Contents for RZQSG71L3V1B

Page 1: ...INSTALLATION MANUAL RZQSG71L3V1B RZQS71D7V1B RZQS71D2V1B RZQS100D7V1B RZQS125D7V1B RZQS140D7V1B Split System air conditioners...

Page 2: ...6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2...

Page 3: ...omo se establece en A y es valorado positivamente por B de acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabele...

Page 4: ...al como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi kat C 11 Information enligt A och g...

Page 5: ...pment Make certain that all electrical work is carried out by quali ed personnel according to the local laws and regulations and this installation manual using a separate circuit Insuf cient capacity...

Page 6: ...ine vapour is present This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Sound level is less than 70 dB A Pro...

Page 7: ...to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the gures for installation of this unit in a place...

Page 8: ...piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical gures used in here represent the dimensions for the 71 100 125 140 class models Figur...

Page 9: ...L4 L7 for double twin These pipe sizes must have the same size as the connected indoor units pipe sizes Branch see marking on gures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L...

Page 10: ...or vertically Length of branch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal REFRIGERANT PIPING Field pipes can be installed...

Page 11: ...now closed Cautions for handling the valve cover The valve cover is sealed where indicated by the arrow Refer to the gure Take care not to damage it After operating the valve be sure to tighten the v...

Page 12: ...easing nitrogen into the piping will create large quantities of oxidised lm on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal oper...

Page 13: ...frigerant unit kg 1 Use a 2 stage vacuum pump with a non return valve which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Evacuate the system from the liquid and gas pipes by using a vacuum pump for more...

Page 14: ...t a malfunction After nishing the pumping down operation make sure to have removed the insulation sheet that was placed in the switch box as a protective measure like in chapter Preliminary measures o...

Page 15: ...Secure the ground wire to the stop valve attachment plate one more time along with the electric wiring and the inter unit wiring Lay the electrical wiring so that the front cover does not rise up whe...

Page 16: ...2 Cut out section 3 Cup washer RZQSG71 RZQS71 RZQS100 RZQS125 RZQS140 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor units for exact value...

Page 17: ...panel with infra red receiver rst 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after nishing the complete test run 6 A complete...

Page 18: ...4T Thermistor coil R5T Thermistor coil middle R6T Thermistor liquid R10T Thermistor n RC Signal receiver circuit S1NPH Pressure sensor high S1PH Pressure switch high TC Signal transmission circuit V1R...

Page 19: ......

Page 20: ...4P342104 1 Copyright 2013 Daikin...

Reviews: