Installation manual

2

Caution

Ground the air conditioner.
Grounding resistance should be according to national
regulations
Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire.
Incomplete grounding may cause electric shocks.

Gas pipe.
Ignition or explosion may occur if the gas leaks.

Water pipe.
Hard vinyl tubes are not effective grounds.

Lightning conductor or telephone ground wire.
Electric potential may rise abnormally if struck by lightning.

Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may cause electric
shocks and fire.

Install drain piping according to this installation manual to
ensure good drainage, and insulate the pipe to prevent
condensation.
Improper drain piping may cause water leakage, and make the
furnitures get wet.

Install the indoor and outdoor units, power wire and connecting
wire at least 1 meter away from televisions or radios to prevent
image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not
be sufficient to eliminate the noise.)

Do not rinse the outdoor unit. This may cause electric shocks or
fire.

Do not install the air conditioner in places such as the following:

Where there is mist of mineral oil, oil spray or vapour for
example a kitchen.
Plastic parts may deteriorate, and cause them to fall out or
water to leak.

Where corrosive gas, such as sulphurous acid gas, is
produced.
Corrosion of copper pipes or soldered parts may cause the
refrigerant to leak.

Where there is machinery which emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and
cause malfunction of the equipment.

Where flammable gases may leak, where carbon fiber or
ignitable dust is suspended in the air or where volatile
flammables, such as thinner or gasoline, are handled.
Such gases may cause a fire.

Where the air contains high levels of salt such as that near
the ocean.

Where voltage fluctuates a lot, such as that in factories.

In vehicles or vessels.

Where acidic or alkaline vapour is present.

This appliance is intended to be used by expert or trained users
in shops, in light industry and on farms, or for commercial use by
lay persons.

Sound level is less than 70 dB(A).

Provide a logbook

In accordance with the relevant national and international codes, it
may be necessary to provide a logbook with the equipment
containing at least 

-

info on maintenance,

-

repair work,

-

results of tests,

-

stand-by periodes,

-

etc...

In Europe, EN378 provides the necessary guidance for this logbook.

B

EFORE

 

INSTALLATION

Precautions for R410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-

Clean and dry

Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-

Tight

Read 

"Precautions on refrigerant piping" on page 6

 carefully and

follow these procedures correctly.

Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant is
in state of gas, its composition changes and the system will not
work properly).

The connected indoor units must be indoor units designed
exclusively for R410A.

Installation

For installation of the indoor unit(s), refer to the indoor unit
installation manual.

Illustrations show class 125 outdoor unit type. Other types also
follow this installation manual.

This outdoor unit requires the pipe branching kit (optional) when
used as the outdoor unit for the simultaneous operation system.
Refer to catalogues for details.

Never operate the unit with a damaged or disconnected
discharge thermistor and suction thermistor, burning of the
compressor may result.

Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.

When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.

Accessories

Check if the following accessories are included with the unit

Since maximum working pressure is 4.0 MPa or 40 bar,
pipes of larger wall thickness may be required. Refer to
paragraph 

"Selection of piping material" on page 5

.

Installation manual

1

Clamp

2

Fluorinated greenhouse gases 
label

1

Multilingual fluorinated 
greenhouse gases label

1

Summary of Contents for RZQSG71L3V1B

Page 1: ...INSTALLATION MANUAL RZQSG71L3V1B RZQS71D7V1B RZQS71D2V1B RZQS100D7V1B RZQS125D7V1B RZQS140D7V1B Split System air conditioners...

Page 2: ...6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2...

Page 3: ...omo se establece en A y es valorado positivamente por B de acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabele...

Page 4: ...al como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi kat C 11 Information enligt A och g...

Page 5: ...pment Make certain that all electrical work is carried out by quali ed personnel according to the local laws and regulations and this installation manual using a separate circuit Insuf cient capacity...

Page 6: ...ine vapour is present This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Sound level is less than 70 dB A Pro...

Page 7: ...to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the gures for installation of this unit in a place...

Page 8: ...piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical gures used in here represent the dimensions for the 71 100 125 140 class models Figur...

Page 9: ...L4 L7 for double twin These pipe sizes must have the same size as the connected indoor units pipe sizes Branch see marking on gures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L...

Page 10: ...or vertically Length of branch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal REFRIGERANT PIPING Field pipes can be installed...

Page 11: ...now closed Cautions for handling the valve cover The valve cover is sealed where indicated by the arrow Refer to the gure Take care not to damage it After operating the valve be sure to tighten the v...

Page 12: ...easing nitrogen into the piping will create large quantities of oxidised lm on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal oper...

Page 13: ...frigerant unit kg 1 Use a 2 stage vacuum pump with a non return valve which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Evacuate the system from the liquid and gas pipes by using a vacuum pump for more...

Page 14: ...t a malfunction After nishing the pumping down operation make sure to have removed the insulation sheet that was placed in the switch box as a protective measure like in chapter Preliminary measures o...

Page 15: ...Secure the ground wire to the stop valve attachment plate one more time along with the electric wiring and the inter unit wiring Lay the electrical wiring so that the front cover does not rise up whe...

Page 16: ...2 Cut out section 3 Cup washer RZQSG71 RZQS71 RZQS100 RZQS125 RZQS140 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor units for exact value...

Page 17: ...panel with infra red receiver rst 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after nishing the complete test run 6 A complete...

Page 18: ...4T Thermistor coil R5T Thermistor coil middle R6T Thermistor liquid R10T Thermistor n RC Signal receiver circuit S1NPH Pressure sensor high S1PH Pressure switch high TC Signal transmission circuit V1R...

Page 19: ......

Page 20: ...4P342104 1 Copyright 2013 Daikin...

Reviews: