background image

10

English

Cut with a tube cutter

Figure 11

2.

Connect the piping.

Remove the upper and lower front panels.

Slide the front panel (lower) along the field piping
until it is far enough away that it will not be affected
by heat from the brazing, as shown in Figure 12.

Braze up to the field piping fitting port while cooling
the sensor and the thermal insulation.

Close the upper and lower front panels once heat
from the brazed areas has dissipated.

When brazing the field piping, cover the pipe insulation and
the thermal sensor inside the insulation with a damp cloth to
prevent any damage to the sensor or the insulation.

Otherwise, the sensor may be damaged by heat of brazing,
which leads to a failure of normal operation.

Field piping fitting port (brazed)

Field piping

Figure 12

3.

After the work is finished, make sure to check that there is
no gas leak.

4.

After checking for gas leaks, be sure to insulate the piping
connections referring to Fig. 13.

Do not leave a gap

Gas piping

Piping heat insulation 
material

Liquid piping

Air 
handler

Figure 13

Be sure to insulate any field piping all the way to the piping
connection inside the unit.  Any exposed piping may cause
condensation or burns if touched.

When  brazing  the  refrigerant  piping,  perform  nitrogen
replacement  first  or  perform  the  brazing  while  feeding
nitrogen into the refrigerant piping.  (Refer to Figure 14.)

Refrigerant piping

Part to be brazed

Taping

Pressure-reducing valve

hands 

valve

Nitrogen

Nitrogen

Figure 14

When brazing pipes while feeding nitrogen inside the piping,
make  sure  to  set  the  nitrogen  pressure  to  2.9  PSI  or  less
using the pressure reducing valve.

(This pressure is such that a breeze is blown to your cheek.)

When  brazing  the  refrigerant  piping,  perform  nitrogen
replacement  first  or  perform  the  brazing  while  feeding
nitrogen into the refrigerant piping.  (Refer to Figure 14.)

When following the Air Tight test procedure during installation
(refer to the outdoor unit installation manual for details), only
pressurize to 450 psig (3.1MPa) when using FTQ.

Summary of Contents for SkyAir FTQ18TAVJUA

Page 1: ...English Fran ais Espa ol ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTU...

Page 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Page 3: ...mmediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage may occur Do not touch the refrigerant pipes during and immediately after op...

Page 4: ...serviceman Improper installation could lead to leaks and in worse cases electric shock or fire Use of unspecified parts could lead to the unit failing leaks and in worse cases electric shock or fire B...

Page 5: ...tion site where the following conditions are fulfilled and meets with your customer s approval Where optimum air distribution can be ensured Where nothing blocks air passage Where condensate can be pr...

Page 6: ...L LEFT INSTALLATION No field modifications are permissible for this application Refer to Figure 7 and 8 for the location of the components referenced in the following steps Drain port labeled B in Fig...

Page 7: ...ew Side view Screw Front view Side view mount mount NOTE DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS 3 Slide the coil as...

Page 8: ...ure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Blower Access Panel Coil Access Panel Tubing Panel UV Knockout Filter Access Panel NOTE If removing only the coil acce...

Page 9: ...nt piping according to the installation environment If the temperature or humidity in the product installation location might reach 86 F or 80 respectively Condensation may form on the surface of the...

Page 10: ...g connections referring to Fig 13 Do not leave a gap Gas piping Piping heat insulation material Liquid piping Air handler Figure 13 Be sure to insulate any field piping all the way to the piping conne...

Page 11: ...roper drainage Some installation may require a field fabricated or field supplied secondary drain pan under the coil cabinet enclosure The installation must include a P style trap that is located as c...

Page 12: ...rmed by an authorized electrician Install a wiring interrupter or ground fault circuit interrupter for the power wiring To avoid short circuiting the power supply wire be sure to use insulated termina...

Page 13: ...r wire connection from the 240V terminal to the 208V terminal on both transformers 8 4 ELECTRICAL CHARACTERISTICS Hz Volts MCA MOP HP FLA Cooling Heating 60 208 230V 4 9 15 1 2 3 9 215 215 60 208 230V...

Page 14: ...fore installing the Heat Kit uninstall the transformer sub assembly Figure 19 Make sure to unplug 12 pin connector before uninstalling the transformer sub assembly Follow the Heat Kit Installation Man...

Page 15: ...RECAUTIONS Daisy chain wiring is needed when using group control and 2 remote controllers at the same time Connect the indoor unit at the end of the crossover wire P1 P2 to remote controller 2 SUB Fig...

Page 16: ...settings may have to be performed using the remote controller depending on the type of installation 1 Make sure the electric component box covers are closed on the indoor and outdoor units 2 Dependin...

Page 17: ...gging and also the time that is set 01 02 0 low high 10000 5000 ON OFF Mode No 10 20 FIRST CODE NO SECOND CODE NO Filter dirt 1 low high 3 Displayed time units hours Filter sign display 2500 1250 9 4...

Page 18: ...CFM can be estimated from the TR formula above See Specification Sheet and or Service Manual for more information 11 21 3 XX XX 01 02 07 08 Heater Operation Electric Heater with Heat Pump not allowed...

Page 19: ...XX Choose dry mode settings as per following table XX 01 02 DRY mode Set Point Room Temperature Set Point became same as cooling mode set point Mode No 14 24 First Code No 5 Second Code No XX 10 ACCES...

Page 20: ...gs 11 TEST RUN Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the...

Page 21: ...R GREEN WH WHITE PU PURPLE LOW VOLTAGE LOW VOLTAGE FIELD HIGH VOLTAGE HIGH VOLTAGE FIELD JUNCTION TERMINAL PLUG CONNECTION EQUIPMENT GND FIELD GROUND 0140A00500 A X1A X3A X38A BS1 X12A X13A HAP X8A TH...

Page 22: ...22 English THIS PAGE LEFT INTENTIONALLY BLANK...

Page 23: ...23 English THIS PAGE LEFT INTENTIONALLY BLANK...

Page 24: ...perly maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in you...

Reviews: