SiUS28-902_B
Troubleshooting by Indication on the Remote Controller
Service Diagnosis
141
Does error
"
U4
" or "
UF
" reoccur?
Is the
resistance value of the
outdoor unit fan motor
normal?
Replace the outdoor unit
fan motor.
Does the fuse (F6U)
have continuity?
Replace the indoor unit
PCB.
External factor (Noise,
etc.)
Replace the fuse.
Is the output
voltage normal?
Replace the outdoor unit
inverter PCB.
Does "
U4
"
error reoccur?
Replace the outdoor unit
inverter PCB.
After turning OFF the power
supply, correctly insert the
connector of the fan motor
and then restore the power.
After turning OFF the power supply,
correctly insert the connector of the
fan motor and then restore the power.
Check the resistance value
of the outdoor fan motor.
Check the fan speed pulse.
A
B
NO
YES
NO
YES
NO
YES
YES
NO
NO
YES