Troubleshooting by Indication on the Remote Controller
SiUS28-902_B
144
Service Diagnosis
3.43 Transmission Error (between Centralized Remote
Controller and Indoor Unit)
Remote
Controller
Display
UE
Applicable
Models
FCQ, FHQ, FAQ, FTQ
Centralized controller
Method of Error
Detection
Micro-computer checks if transmission between indoor unit and centralized remote controller is
normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Transmission error between optional controllers for centralized control and indoor unit
Connector for setting main controller is disconnected.
Defective PCB for centralized remote controller
Defective indoor unit PCB