SiUS28-902_B
Troubleshooting by Indication on the Remote Controller
Service Diagnosis
125
3.29 Low Pressure Sensor Abnormality
Remote
Controller
Display
JC
Applicable
Models
RZR, RZQ
Method of Error
Detection
The error is detected from the pressure detected by the low pressure sensor.
Error Decision
Conditions
When the low pressure sensor is short circuit or open circuit
Supposed
Causes
Defective low pressure sensor
Connection of high pressure sensor with wrong connection.
Defective outdoor unit PCB