Si12-308
Control Specification
Function and Control
107
3.15
Wiring-Error Check
Outline
The convenient Wiring Error Check function is designed for the microcomputer to correct wiring
errors itself.
If local wiring is unclear in the case of buried piping, for example, just press the wiring error
check switch that is behind the right-hand panel of the outdoor unit. Even if the connections for
Room A and Room B are confused, the system may run without a hassle. Note that this check
function does not work in the following cases.
For about 30 seconds after the power is turned on (during initial setup).
For 3-minute standby period after the compressor has stopped.
When the outdoor air temperature is below 5°C.
If the indoor unit is in trouble (also in case of all-room transmission failure).
When the piping and wiring are perfect, there is no need to use this function.
Operation
1. Remove the 5 screws from the service panel (right side panel) and detach the panel.
2. Press the wiring error check switch on the service monitor PCB, and the wiring error check
function is activated.
3. In about 10-15 minutes, the checking will end automatically.
4. When the checking is over, the service monitor LED indicators start flashing.
Self-correction complete…The LED indicators 1 ~ 4 flash one after another.
Self-correction impossible…The LED indicators flash all at the same time.
Transmission failure occurs at any of the indoor units.
The indoor unit heat exchanger thermistor is disconnected.
An indoor unit is in trouble (if a trouble occurs during the wiring error checking).
Emergency stop…Any of the LED indicators 1 ~ 4 stays on.
Note:
1. It takes about 10-15 minutes (after pressing the wiring error check switch) to complete the
checking. (Wrong wiring between the upper and lower units cannot be self-corrected.)
2. Wrongly connected liquid and gas pipes cannot be self-corrected either. Be sure to make the
liquid pipe and the gas pipe in pairs.
3. To forced-terminate the wiring error check procedure halfway, press the wiring error check
switch again.
In this case, the microcomputer's memory gets back to its initial status (Room A wiring
→
Port A piping, Room B wiring
→
Port B piping).
4. In replacing the outdoor unit PCB, be sure to use this function.
5. Make the power slide setting after doing the wiring error checking. (Otherwise, if the wiring is
reversed, the air-conditioners being connected are set up in the reverse way.)
Basic Knowledge
This function works in this way. Refrigerant is let flow from Port A and on. The temperatures
of the indoor unit heat exchanger thermistors are detected one by one to check up the
matching between the pipes and wiring.
With this function on, freezing (crackling) noise may be heard from the indoor unit. This is
not a problem. (This is because the heat exchange temperature is made to drop below 0°C
in order to increase the detection accuracy.)
The indoor fan is made to turn on and off at the same time.
LED
1
2
3
4
Judgment
Status
All flashing at once
Self-correction impossible
Flashing one after another
Self-correction complete
Summary of Contents for Super Multi NX B series
Page 7: ...Si12 308 vi Table of Contents ...
Page 29: ...List of Functions Si12 308 18 List of Functions ...
Page 71: ...Specifications Si12 308 60 Specifications ...
Page 175: ...Instruction Si12 308 164 System Configuration ...
Page 227: ...Check Si12 308 216 Service Diagnosis ...
Page 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Page 299: ...Si12 308 iv Index ...