Troubleshooting
Si12-308
196
Service Diagnosis
Troubleshooting
Check No.6
Refer to P.210
P4
: Radiation fin thermistor
J3
: Discharge pipe temperature thermistor
J6
: Outdoor unit heat exchanger temperature thermistor
J8
: Liquid pipe thermistor
J9
: Gas pipe thermistor
H9
: Outdoor temperature thermistor
Turn on the power again.
Reconnect.
Reconnect.
Replace defective one(s) of
the following thermistors.
l
Radiation fin thermistor
l
Discharge pipe
temperature thermistor
l
Outdoor unit heat
exchanger temperature
thermistor
l
Liquid pipe thermistor
l
Gas pipe thermistor
l
Outdoor temperature
thermistor
Replace the following
thermistor.
l
Indoor unit heat
exchanger thermistor
Replace the outdoor unit
PC board. (Replace the
indoor unit PC board.)
(Q0357)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Error displayed again
on remote controller?
NO
YES
YES
YES
NO
Indoor unit
heat exchanger thermistor
functioning?
NO
Connector or thermistor
disconnected?
NO
YES
J3 error if discharge pipe
thermistor temperature is
smaller than condenser
thermistor temperature
Cooling: Outdoor unit heat
exchanger thermistor
Heating: Indoor unit heat
exchanger thermistor
Normal?
Check No. 6
Check the thermistor resistance
value.
Check No. 6
Check the indoor unit heat
exchanger thermistor resistance
value in the heating mode.
Summary of Contents for Super Multi NX B series
Page 7: ...Si12 308 vi Table of Contents ...
Page 29: ...List of Functions Si12 308 18 List of Functions ...
Page 71: ...Specifications Si12 308 60 Specifications ...
Page 175: ...Instruction Si12 308 164 System Configuration ...
Page 227: ...Check Si12 308 216 Service Diagnosis ...
Page 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Page 299: ...Si12 308 iv Index ...