Outdoor Unit (80 / 90 Class)
Si12-308
238
Removal Procedure
1.9
Removal of
Solenoid Valve
and
Four Way Valve
Procedure
Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
Remove the outer panels.
Caution
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the gas
welding rod.
1. Removing the solenoid
valve
1
Remove 1 screw of the
solenoid valve coil.
Before taking this
procedure, make sure
there is no refrigerant gas
left in the refrigerant
pipes.
2
Disconnect the 2
brazed points (a) and
(b) in this order.
Warning
If refrigerant gas leaks during
the job, ventilate the room.
(Bear in mind that if the
refrigerant gas is exposed to
open flames, noxious gas may
be generated.)
2. Removing the four way
valve
Reassembling precautions
Wrap the solenoid valve body
with wet cloth. Splash water
over the cloth before it is dried
to prevent the valve from being
overheated.
1
Remove 1 screw of the
four way valve coil.
Summary of Contents for Super Multi NX B series
Page 7: ...Si12 308 vi Table of Contents ...
Page 29: ...List of Functions Si12 308 18 List of Functions ...
Page 71: ...Specifications Si12 308 60 Specifications ...
Page 175: ...Instruction Si12 308 164 System Configuration ...
Page 227: ...Check Si12 308 216 Service Diagnosis ...
Page 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Page 299: ...Si12 308 iv Index ...