Specifications
Si12-308
34
Specifications
1.2
Outdoor Units - Cooling Only
50Hz 220-230-240V / 60Hz 220-230V
Note:
1. The data are based on the conditions shown in the table below.
Model
2MKD58BVM
3MKD58BVM
Cooling Capacity
kW
—
—
Power Consumption
W
—
—
Running Current
A
—
—
Casing Color
Ivory White
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Hermetically Sealed Swing Type
Model
2YC32WXD
2YC32WXD
Motor Output
W
980
980
Refrigerant Oil
Model
SUNISO 4GSD.I.
SUNISO 4GSD.I.
Charge
L
0.65
0.65
Refrigerant
Type
R22
R22
Charge
kg
2.0
2.0
Air Flow Rates
m³/min
H
44
44
L
37
37
cfm
H
1,270
1,270
L
1,068
1,068
Fan
Type
Propeller
Propeller
Motor Output
W
53
53
Running Current
A
H: 0.24 / L: 0.17
H: 0.24 / L: 0.17
Power Consumption
W
H: 44 / L: 27
H: 44 / L: 27
Starting Current
A
6.9
6.5
Dimensions (H×W×D)
mm
735×936×300
735×936×300
Packaged Dimension
mm
960×357×784
960×357×784
Weight
kg
55
55
Gross Weight
kg
59
59
Operation Sound
dBA
46
46
Piping Connection
Liquid
mm
φ
6.4×2
φ
6.4×3
Gas
mm
φ
12.7×2
φ
12.7×3
Drain
mm
φ
16.0
φ
16.0
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
No. of Wiring Connection
3 for Power Supply, 4 for Interunit Wiring
3 for Power Supply, 4 for Interunit Wiring
Max. Interunit Piping Length
m
35 (for Total of Each Room)
45 (for Total of Each Room)
m
25 (for One Room)
25 (for One Room)
Amount of Additional Charge
g/m
Charge Less
Charge Less
Max. Installation Height Difference
m
15 (between Indoor Unit and Outdoor Unit)
15 (between Indoor Unit and Outdoor Unit)
m
7.5 (between Indoor Units)
7.5 (between Indoor Units)
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling
Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB
5.0m
Summary of Contents for Super Multi NX B series
Page 7: ...Si12 308 vi Table of Contents ...
Page 29: ...List of Functions Si12 308 18 List of Functions ...
Page 71: ...Specifications Si12 308 60 Specifications ...
Page 175: ...Instruction Si12 308 164 System Configuration ...
Page 227: ...Check Si12 308 216 Service Diagnosis ...
Page 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Page 299: ...Si12 308 iv Index ...