Troubleshooting for Outdoor Unit
SiBE121021_C
342
Service Diagnosis
Troubleshooting
Check No.01
Refer to P.362
Check No.12
Refer to P.364
Check No.17
Refer to P.368
Check No.18
Refer to P.368
Check No.19
Refer to P.369
(R14558)
Caution
Replace the fan motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB.
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 17
Check the
installation condition.
Check No. 19
Check the outdoor fan.
Check No. 18
Check the discharge
pressure.
Check No. 12
Check the electronic
expansion valve.
Check No. 01
Check the outdoor heat
exchanger thermistor.