Code Indication on Remote Controller
SiBE121021_C
306
Service Diagnosis
4. Code Indication on Remote Controller
4.1
RA Indoor Unit - F(C)TXG, FTXS, ATXS, FVXS, FLK(X)S,
FDK(X)S Series
4.2
SA Indoor Unit - FFQ, FCQ, FDBQ, FBQ, FHQ Series
: Error code displays automatically and system stops.
Inspect and repair it.
: In the case of the shaded error codes, “inspection” is not displayed. The system
operates, but be sure to inspect and repair it.
Error Codes
Description
Reference Page
00
Normal condition
—
A1
Indoor unit PCB abnormality
A5
Freeze-up protection control or heating peak-cut control
A6
Fan motor or related abnormality
DC motor (wall, floor standing)
AC motor (duct, floor / ceiling)
C4
Indoor heat exchanger thermistor or related abnormality
C7
Front panel open / close fault (FTXG and CTXG series)
C9
Room temperature thermistor or related abnormality
U4
Signal transmission error (between indoor unit and outdoor unit)
UA
Unspecified voltage (between indoor unit and outdoor unit)
Error Codes
Description
Reference Page
00
Normal condition
—
A1
Indoor unit PCB abnormality
A3
Drain water level system abnormality
A6
Fan motor or related abnormality
A7
Swing motor lock (FHQ series)
AF
Drain system abnormality
C4
Indoor heat exchanger thermistor or related abnormality
C9
Room temperature thermistor or related abnormality
CJ
Remote controller thermistor abnormality
U5
Signal transmission error (between indoor unit and remote
controller)
U8
Signal transmission error (between MAIN remote controller and
SUB remote controller)
UA
Field setting abnormality