SiBE121021_C
Specifications
Specifications
45
1.4
Heat Pump - Outdoor Unit
50 Hz, 230 V
Note:
The data are based on the conditions shown in the table below.
Model
3MXS52E3V1B
Cooling
Heating
Casing Color
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Model
2YC36BXD
Motor Output
W
1,100
Refrigerant Oil
Model
FVC50K
Charge
L
0.65
Refrigerant
Type
R-410A
Charge
kg
2.0
Airflow Rates
H
m³/min
45
45
L
45
41
H
cfm
1,589
1,589
L
1,589
1,448
Fan
Type
Propeller
Motor Output
W
53
Running Current
A
H: 0.33 / L: 0.29
Power Consumption
W
H: 43 / L: 34
Starting Current
A
6.2
Dimensions (H × W × D)
mm
735 × 936 × 300
Packaged Dimensions (H × W × D)
mm
797 × 992 × 390
Weight (Mass)
kg
49
Gross Weight (Gross Mass)
kg
56
Operation Sound
dB(A)
46
47
Sound Power
dB(A)
59
60
Piping
Connection
Liquid
mm
φ
6.4 × 3
Gas
mm
φ
9.5 × 2
, φ
12.7 × 1
Drain
mm
φ
18.0
Heat Insulation
Both Liquid and Gas Pipes
No. of Wiring Connection
3 for Power Supply, 4 for Interunit Wiring
Max. Interunit Piping Length
m
50 (for Total of Each Room)
m
25 (for One Room)
Amount of Additional Charge
g/m
20 (30m or more)
Max. Installation Height Difference
m
15 (between Indoor Unit and Outdoor Unit)
m
7.5 (between Indoor Units)
Drawing No.
3D054327#1
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling
Heating
Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB
Indoor ; 20°CDB
Outdoor ; 7°CDB / 6°CWB
7.5 m