1
[Operation Manual]
60/61
DAIKIN INDUSTRIES, LTD.
2-7 Alarm classification [4]
The above chart shows the case where
“
P03
”
(Pressure switch display hold setting) is [1] or [2].
When
“
P03
”
is [0], an actual pressure value is displayed.
When the stop command is activated by the start/stop signal, the pressure switch is in the normal
condition.
The
“
P01
”
and
“
P02
”
settings (above [1] and [2]) can be changed in the setting mode.
For the setting procedure and setting range, see
“
Operating procedure for each mode: b) Setting mode
”
on
p. 39.
Note) For the purpose of explanation, the above
“
2-7 Alarm classification [4]
”
chart shows the case where
the pressure switch is activated without a dead zone. Actually, however, the pressure switch has a dead
zone of approx. 0.5 MPa.
Note) Set the time interval after a stop signal at 0.5 seconds or longer.
Start/stop signal
Mode
Display
Alarm/Warning
(Relay output)
H: Normal
[1]
“
P01
”
pressure switch setting
[2]
“
P02
”
pressure switch delay time [*]
[*]
[Note]
H: Stop command
L: Operation command
L: Abnormal
Actual pressure display