Page | 33
Menu
Factory Default
Setting
Range
Unit
Authorisation
Minimum
Maximum
R*
W*
Evp Pmp Ctrl
#1 Only
#1 Only
#2 Only
Auto
#1 Primary
#2 Primary
--
S
S
Evap Recirc Tm
30
0
300
s
S
S
Evap Var Flow
No
No
Yes
--
S
S
Var Fl Unload Adj
2
1
5
--
S
S
Evap Nom DT
5.6
3.3
8.9
dK
S
M*
Evap Pmp 1 Hrs
--
0
999999
hour
U
M
Evap Pmp 2 Hrs
--
0
999999
hour
U
M
Water Valve En
No
No
Yes
--
S
S
Remote Srv En
Disable
Disable
Enable
--
U
U
3.2. Unit Set-Up
Available Modes
Cool
Cool
Cool/Ice w/Glycol
Cool/Heat
/Cool/Ice/Heat w/Glycol
--
U
S
Unit Type
Normal
Normal
Low Oat
Super Low
--
S
M
Start Up DT
2.7
0.0
5.0
dK
U
S
C Shut Dn DT
1.5
0.0
1.7
dK
U
S
H Shut Dn DT
2.5
0.0
2.7
dK
U
S
Stg Up DT
0.5
0.0
1.7
dK
U
S
Stg Dn DT
0.7
0.0
1.7
dK
U
S
Max Pulldn
2.5
0.5
2.5
℃/mi
n
U
S
Stg Up Delay
5
0
60
min
U
S
Stg Dn Delay
3
3
60
min
U
S
Strt Strt Dly
20
15
60
min
S
M
Stop Strt Dly
5
3
20
min
S
M
Pumpdn Press
100.0
70.0
280.0
kPa
S
S
Pumpdn Time
60
0
180
s
S
S
Lt Ld Stg Dn %
40.0
25.0
50.0
%
S
S
Hi Ld Stg Up %
80.0
50.0
100.0
%
S
S
Liq Inject Act
85.0
80.0
100.0
℃
S
S
PVM Config
Single Point
Single Point
Multi Point
None
--
S
M
Max Ckts Run
1
1
2
--
S
S
C1 Sequence #
1
1
2
--
S
S
C2 Sequence #
1
1
2
--
S
S
Auto Restart
Yes
No
Yes
U
S
Ice Cycle Dly
12
1
23
hour
U
S
Ext Fault Cfg
Event
Event
Alarm
--
S
S
EnOilHeatCtrl
Enable
Disable
Enable
--
M
M
Oil Heating Control Set
Discharge Temp.
50.0
30.0
70.0
℃
M
M
Summary of Contents for UAA-ST3M