38 |
P a g e
Menu
Factory Default
Setting
Range
Unit
Authorisation
Minimum
Maximum
R*
W*
EXV Configuration
Drive Current
140
0
150
mA
S
S
Hold Current
75
150
mA
S
S
Drive Speed
150
300
Hz
S
S
Over Close Steps
100
500
--
S
S
Over Open Steps
100
500
--
S
S
Dead Time Sync
5
60
min
S
S
Comp Size
HSS3221
HSS3219
、
HSS3220
、
HSS3221
、
HSS3222
、
HSS3223
、
HSS4224
、
HSS4225
、
HSS4226
、
HSS4227
--
U
S
4.6.Calibrate Sensors
Evp Pr Offset
0.0
-100.0
100.0
kPa
S
S
Cnd Pr Offset
0.0
Oil Pr Offset
0.0
Suction Offset
0.0
-5.0
5.0
dK
S
S
Disch Offset
0.0
De-Ice 1 Offst
0.0
De-Ice 2 Offst
0.0
Sld Pos Min mA
4.0
0.0
22.0
mA
S
S
Sld Pos Max mA
20.0
0.0
22.0
mA
S
S
CompCurrMin mA
4.0
0.0
22.0
mA
S
S
CompCurrMax mA
20.0
0.0
22.0
mA
S
S
5.Time Until Restart
C1 Cycle Tmr Clr
Off
Off
On
--
S
S
C2 Cycle Tmr Clr
Off
Off
On
--
S
S
6.Alarms
6.1.Alarm Active
AlmClr
Off
Off
On
--
N
N
6.2.Alarm Log
LogClr
Off
Off
On
--
N
M
6.3.ExportHisRecord
ExportHisData
Off
Off
On
--
S
S
ClearHisData
Off
Off
On
--
S
S
7.Scheduled Maintenance
Next Maint
Jan
Jan
Dec
--
N
S
2009
2009
2100
--
N
S
Support Reference
(999)555-5555
--
--
N
S
8.Save/Restore
Save Params
No
No
Yes
--
M
M
Rstr Params
No
Save To File
No
Rstr From File
No
Rstr Factory
No
Summary of Contents for UAA-ST3M