Page | 43
No.
Menu
Property
10
UnitOffEvpLvgWTempFault
Check whether leaving water temperature
sensor is working properly.
Check whether leaving water temperature
sensor wiring is correct.
11
StartInhbtAmbTempLowLimitActive
Start the unit only when the ambient
temperature meets the related requirements
(cooling > 4°C).
12
C1/2OffStrtFailEvpPrLowLimitActive
Check whether there is refrigerant leakage.
13
C1/2Cmp1
OffCndPressHighLimitActive
Check that the working conditions meet
therelated requirements.
Refrigerant charge meets the requirement on
the nameplate, not overcharged.
14
C1/2Cmp1
OffEvpPressLowLimitActive
Check that the working conditions meet the
related requirements.
Check whether there is refrigerant leakage.
15
C1/2Cmp1 OffPrRatioLoOffNormal
Check that the working conditions meet the
related requirements.
For standard cooling operation: ambient
temperature: 5 ~50°C; leaving water: 4 ~ 35°C.
For
low
ambient
temperature
cooling
operation: ambient temperature: -10 ~ 50°C;
leaving water: 4 ~ 35°C.
16
C1/2Cmp1 OffMechPressHiOffNormal
Check that the working conditions meet the
related requirements.
Refrigerant charge meets the requirement on
the nameplate, not overcharged.
Check whether the high-pressure switch is set
to 20.5 bars.
17
C1/2Cmp1
OffDischTmpHighLimitActive
Check whether the spray pipeline is blocked.
Check whether there is refrigerant leakage.
Check that the working conditions meet the
related requirements.
18
C1/2Cmp1 OffOilFeedPOffNormal
Exchange the oil filter of the compressor.
19
C1/2Cmp1 OffStarterFltOffNormal
Check the wiring of the compressor.
20
C1/2 OffNoPressChgStartOffNormal
Check whether there is refrigerant leakage.
Check the suction and discharge pressure
sensors and its wiring.