Page | 47
Alarm
Evaporator Water Temperature
Low
Code: UnitOffEvapWaterTmp
LoOffNormal
Category:
Critical
Trigger
Action
Unit immediate shutdown
Reset method
Manual reset
Reset
Condition
Entering water temp.
≥
2.2
o
C
Leaving water temp.
≥
2.2
o
C
Solution
Check and make sure water flow meet recommended requirement
Yes
No
Yes
Yes
No
Confirm Time = 3 sec?
Alarm
Evap entering/leaving water
temp sensor = Alarm?
Evap entering/leaving water
temp ≤ 2.2
o
C?
Alarm:
UnitOffEvpEntWTempOffNormal /
UnitOffEvpLvgWTempFault
Yes
Summary of Contents for UAA-ST3M