Page | 55
Alarm
C#Fan Evap Pressure Low Start Fail
Code:
C#OffStrtFailEvpPrLowLimitActive
Category:
Event
Trigger
Action
Corresponding system immediate shutdown
Reset method Manual reset
Reset
Condition
C#Evap pressure > Low pressure unload SP
Solution
Check for refrigerant leakage
Check for filter drier clog
Check for pressure transducer (suction and discharge) condition
C#Compressor state = ON?
Alarm
Yes
No
Yes
Cond. saturated temp
< 15.5°C?
Evap pressure
< low pressure unload SP?
Confirm Time
= 60 sec?
Yes
No
No
No
Summary of Contents for UAA-ST3M