60 |
P a g e
Alarm
C#
Compressor#
off
hi
discharge
temperature
Code:
C#Cmp#OffHighDischTmpOffN
ormal
Category:
Event
Trigger
Action
Corresponding system pump down shutdown
Reset method
Manual reset
Reset
Condition
Disch temp < Hi disch temp SP
Solution
Check refrigerant charge
Check filter drier for clog
Check chiller operating environment
C#Compressor state = ON?
Alarm
Yes
No
Disch temp sensor = Alarm?
No
Disch temp
> Hi Disch temp SP?
Yes
Alarm:
C#Cmp#OffDischTmpFault
Summary of Contents for UAA-ST3M
Page 2: ......