64 |
P a g e
Alarm
C# off no pressure at start
Code:
C#OffNoPressAtStartOffNormal
Category:
Event
Trigger
Action
Corresponding system immediate shutdown
Reset method
Manual reset
Reset
Condition
-
Solution
Check refrigerant leakage
Check discharge and suction pressure transducer condition and its wiring
C#Compressor state = ON?
Alarm
Yes
Yes
Yes
Evap/Cond. pressure
< 35kPa?
No
No
VFD unit
No