80 |
P a g e
No.
Object Name
Obj
Instance
Object type
Level
<4>
Details
R/W
Unit
Notes
47
HRLwt2
507
analog_input
Single
HR LWT2
(precision 0.1
℃
)
R
ºC
48
ACSysEnableStp
3
binary_value
ACS
Air-condition
System On/Off
0: Off (Inactive)
1: On (Active)
R/W
--
49
ACSysMasterEnableStp
4
Master
Air-condition
System Master
On/Off
0: Off (Inactive)
1: On (Active)
R/W
--
50
ACSysSlaveEnableStp
5
Slave
Air-condition
System Slave
On/Off
0: Off (Inactive)
1: On (Active)
R/W
--
51
SlaveCir1CompStatus
30
Slave
System #1 Comp
0: Off (Inactive)
1: On (Active)
R
--
52
SlaveCir2CompStatus
31
System #2 Comp
0: Off (Inactive)
1: On(Active)
R
--
53
ACSysAlarm
30
binary_input
ACS
Air-condition
System Alarm
0: No
Alarm(Inactive)
1: Alarm(Active)
R
--
54
SlaveAlarmOutput
31
Slave
Chiller Alarm
0: No
Alarm(Inactive)
1: Alarm(Active)
R
--
55
SlaveEvapFlowStatus
32
Evap Flow Status
0: Off(Inactive)
1: On(Active)
R
--
56
SlaveEvapPump1State
33
Evap Pump #1
Status
0: Off(Inactive)
1: On(Inactive)
R
--
57
SlaveEvapPump2State
34
Evap Pump #1
Status
0: Off(Inactive)
1: On(Inactive)
R
--
58
SlaveChillerStatus
10
Slave
Chiller Status
1:Off
3:Start
4:PumpDown
5:Testing
R
--
59
SlaveStatus
11
Unit Actual Status
(precision: 1)
R
--
60
SlaveCir1Status
12
System #1 Status
(precision: 1)
R
--
61
SlaveCir2Status
13
System #2 Status
(precision: 1)
R
--
62
ACSysStatus
191
ACS
Air-condition
System Actual
Status
(precision: 1)
R
--
63
ACSysFltCode
30
ACS
Air-condition
System Fault Code
(precision: 1)
R
--
64
ACSActualCapacity
182
Air-condition
System Capacity
(rang:
0.0%~100.0%)
R
%
65
SlaveChillerCapacity
31
analog_value
Slave
Chiller Actual
Capacity
(rang:
0.0%~100.0%)
R
%
66
SlaveEcpmpHrs1
32
Evap Pump #1 Run
Hours
(precision: 1 Hour)
R
Hour
67
SlaveEcpmpHrs2
33
Evap Pump #2 Run
Hours
(precision: 1 Hour)
R
Hour