10

Model

Power cable

(mm

2

)

Breaker

capacity (A)

Over current 

protection switch (A)

Earth cable

(mm

2

)

UATQ60C

2.5

20

20

2.5

UATQ90C

4

32

32

4

UATQ120C

6

32

32

6

UATQ150C

10

40

40

10

UATQ180C

10

50

50

10

UATQ210C

16

63

63

16

UATQ240C

16

63

63

16

UATQ300C

25

80

80

25

Note:

A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated 
in fixed wiring in accordance with local and national legislation.
The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or 
HRC fuse.
 Fix the power supply wiring to control module. Connect control wiring to control terminal block through the 
control box’s hole. 
Earth wiring must be connected. 
 The power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used in 
protective tube.


Model: UATQ120/150/180/210/240/300C

Control wire

Terminal 
block

Power cable

CONTROL 

BOX

(2) Wiring connection to unit

Route the power supply wires and control wire through the holes in the unit.
Remove the service panels and connect the units power supply wires to terminal block inside the control box, as 
shown.
Make use of push releasable cable ties which are located at the bottom of control box to hold the power supply 
wires properly


Control Module

(3) Wiring Example And Selection Of Circuit Breaker

Note:

While installing the circuit breaker onto the unit, make sure that the screws do not damage the components 
(e.g. coil) inside the unit.

Model: UATQ60/90C

Control wire

Power cable

CONTROL BOX

Terminal block

Control 

Module

1-IM-5RTC-0315(6)-DAIKIN-EN.indd10   10

1-IM-5RTC-0315(6)-DAIKIN-EN.indd10   10

7/10/20   10:35:15 AM

7/10/20   10:35:15 AM

Summary of Contents for UATQ60C

Page 1: ...Air Conditioner English Model UATQ60C UATQ90C UATQ120C UATQ150C UATQ180C UATQ210C UATQ240C UATQ300C IM 5RTC 0315 6 DAIKIN Part No R08019042228F 1 CVR IM 5RTC 0315 6 DAIKIN_EN 1 1 1 CVR IM 5RTC 0315 6...

Page 2: ...1 CVR IM 5RTC 0315 6 DAIKIN_EN 2 2 1 CVR IM 5RTC 0315 6 DAIKIN_EN 2 2 7 10 20 10 40 17 AM 7 10 20 10 40 17 AM...

Page 3: ...75 350 Weight of corner kg Total weight kg A B C D 82 108 108 82 380 84 84 1112 1112 94 142 1530 508 172 1280 1150 1300 770 730 A B D 1112 84 84 94 1112 94 142 1520 B A D 730 770 50 50 270 184 674 130...

Page 4: ...160 165 165 650 Weight at corner kg Total weight kg A B C D 190 190 230 230 840 1965 1390 1988 1052 1630 48 150 50 350 165 700 125 83 83 1800 94 1800 94 142 830 D C B A 994 1045 994 B C D A 1905 48 1...

Page 5: ...30 50 150 2110 150 160 2110 160 720 1320 70 407 1140 90 245 2430 1950 2410 English Model UATQ210 240C Model Weight at corner kg Total weight kg A B C D UATQ210C 238 238 227 227 930 UATQ240C 240 240 23...

Page 6: ...power resumes posing a hazard to service personnel or the user Do not operate any heating apparatus too close to the air conditioner unit Don t use joined and twisted wires for incoming power supply...

Page 7: ...5 7 9 6 3 3 3 1 No Item Description 1 Compressor 2 High Pressure Switch 3 Access Valve 4 Outdoor Heat Exchanger 5 Indoor Heat Exchanger 6 Filter Dryer 7 Thermal Expansion Valve TXV 8 Low Pressure Swit...

Page 8: ...OLYBAG REMOVE TOP WOODEN CRATE REMOVE ALL CARTON BOARDS FASTEN SCREWS BACK ON PANEL 4 CORNERS REMOVE BOTTOM WOODEN CRATE 1 2 3 4 5 6 Model UATQ60 90 120 150 180 210 240 300C 1 IM 5RTC 0315 6 DAIKIN EN...

Page 9: ...ral public B Duct Construction This unit are equipped with supply and return air openings Duct connection to the unit should be made with duct flanges and secured directly to the air openings with fle...

Page 10: ...no leakage and that the water drains off properly 3000 1200 1200 Evaporator coil motor service Air filter service 1200 Condenser air inlet The drain piping should have a drain trap Drain piping The d...

Page 11: ...60 3304 3587 3776 4248 Condenser air flow CFM 5100 7500 9900 13800 12230 21500 22000 L s 2407 3540 4672 6513 5772 10147 10383 Control Sequential Controller Compressor Type Quantity Scroll 1 Scroll 2 A...

Page 12: ...ord must be equivalent to H07RN F which is the minimum requirement and to be used in protective tube Model UATQ120 150 180 210 240 300C Control wire Terminal block Power cable CONTROL BOX 2 Wiring con...

Page 13: ...re to perform curling Problems with the work may cause heat and fires Stripping wire at terminal block Good Wrong Strip wire end to this point Excessive strip length may cause electrical shock or leak...

Page 14: ...ith condition 29 C DB 19 C WB indoor 46 C DB outdoor All the additional capacitor has to be field supplied based on the suggested capacitor size in table to achieve 0 9F All calculations subjected to...

Page 15: ...Pressure Pascal 50 85 150 200 250 RPM PO kW RPM PO kW RPM PO kW RPM PO kW RPM PO kW 3300 579 0 46 667 0 59 797 0 79 894 0 97 984 1 17 4400 657 0 85 728 1 00 834 1 25 918 1 46 998 1 68 5300 729 1 29 78...

Page 16: ...Cubic feet per minute PO Motor power output Airflow rate CFM External Static Pressure Pascal 50 100 165 200 250 RPM PO kW RPM PO kW RPM PO kW RPM PO kW RPM PO kW 5800 546 0 97 623 1 21 720 1 54 767 1...

Page 17: ...se phase Switch off the unit Check the 3 phase wiring T phase missing Switch off the unit Check the 3 phase wiring S phase missing Switch off the unit Check the 3 phase wiring R phase missing Switch o...

Page 18: ...r some simple troubleshooting tips Problem Causes Action Unit does not run Power failure Press the ON OFF after power restore Fuse blown or circuit breaker tripped Replace fuse or reset circuit breake...

Page 19: ...1 CVR IM 5RTC 0315 6 DAIKIN_EN 3 3 1 CVR IM 5RTC 0315 6 DAIKIN_EN 3 3 7 10 20 10 40 17 AM 7 10 20 10 40 17 AM...

Page 20: ...aikinmea com Zandvoordestraat 300 B 8400 Oostende Belgium Importer for Turkey Allianz Plaza Kucukbakkalkoy Mah Kay sdagi Cad No 1 34750 Atasehir ISTANBUL TURKIYE Head office Umeda Center Bldg 2 4 12 N...

Page 21: ...URKIYE Head office Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global Lot 6...

Page 22: ...0 CVR IM 5RTC 0315 6 DAIKIN AR 3 3 0 CVR IM 5RTC 0315 6 DAIKIN AR 3 3 7 10 20 10 39 29 AM 7 10 20 10 39 29 AM...

Page 23: ...16 40 2 ON OFF 3 3 UATQ210 240C 0 IM 5RTC 0315 6 DAIKIN AR indd16 16 0 IM 5RTC 0315 6 DAIKIN AR indd16 16 7 10 20 12 27 41 PM 7 10 20 12 27 41 PM...

Page 24: ...PW P_R P_S P_T 3 T 3 S 3 R 3 T S 3 PP01 1 81 71 LED R 2 UATQ60 90C LED PW P_S P_T 3 T 3 S 3 R 3 UATQ120 150 180 210 240 300C 0 IM 5RTC 0315 6 DAIKIN AR indd15 15 0 IM 5RTC 0315 6 DAIKIN AR indd15 15 7...

Page 25: ...77 1046 5 16 1092 5 55 10750 952 5 32 50 100 165 200 250 RPM PO kW RPM PO kW RPM PO kW RPM PO kW RPM PO kW 5800 546 0 97 623 1 21 720 1 54 767 1 72 835 1 99 7600 618 1 71 679 2 00 758 2 41 798 2 62 8...

Page 26: ...5 1 10 1607 1 21 1687 1 31 1766 1 42 2800 3300 50 85 150 200 250 RPM PO kW RPM PO kW RPM PO kW RPM PO kW RPM PO kW 3300 579 0 46 667 0 59 797 0 79 894 0 97 984 1 17 4400 657 0 85 728 1 00 834 1 25 918...

Page 27: ...UATQ120C 10 UATQ150C 20 UATQ180C 20 UATQ210C 25 UATQ240C 30 UATQ300C 30 19 29 ISO 46 0 9 b UATQ60 90 UATQ120 150 180 UATQ210 240 300 0 IM 5RTC 0315 6 DAIKIN AR indd12 12 0 IM 5RTC 0315 6 DAIKIN AR ind...

Page 28: ...7 4 a 4 3 6 4 5 1 1 2 4 4 7 UATQ120 150 180C UATQ210 240 300C 1 1 4 1 4 7 6 5 3 4 4 4 2 3 6 4 7 5 1 1 1 4 1 4 4 1 0 IM 5RTC 0315 6 DAIKIN AR indd11 11 0 IM 5RTC 0315 6 DAIKIN AR indd11 11 7 10 20 12...

Page 29: ...UATQ150C 10 40 40 10 UATQ180C 10 50 50 10 UATQ210C 16 63 63 16 UATQ240C 16 63 63 16 UATQ300C 25 80 80 25 HRC H07RN F UATQ120 150 180 210 240 300C UATQ60 90C 0 IM 5RTC 0315 6 DAIKIN AR indd10 10 0 IM 5...

Page 30: ...0 x 4 895 x 685 x 4 834 x 760 x 4 1040 x 750 x 4 1040 x 1050 x 4 UATQ60C UATQ90C UATQ120C UATQ150C UATQ180C UATQ210C UATQ240C UATQ300C V Ph Hz 380 415 3N 50 Comp A 15 20 15 15 19 19 20 20 23 23 25 25...

Page 31: ...1 A 3000 1200 1200 1200 A B C mmAq ESP 70 A 2C B 2 X ESP C 1200 1200 1200 3000 UAT60 90C UATQ120 150 180 210 240 300C 0 IM 5RTC 0315 6 DAIKIN AR indd8 8 0 IM 5RTC 0315 6 DAIKIN AR indd8 8 7 10 20 12...

Page 32: ...7 A B C 4 4 UATQ210 240C 2000 4 0 IM 5RTC 0315 6 DAIKIN AR indd7 7 0 IM 5RTC 0315 6 DAIKIN AR indd7 7 7 10 20 12 27 49 PM 7 10 20 12 27 49 PM...

Page 33: ...6 UATQ60 90 120 150 180 210 240 300C 4 1 2 3 4 5 6 0 IM 5RTC 0315 6 DAIKIN AR indd6 6 0 IM 5RTC 0315 6 DAIKIN AR indd6 6 7 10 20 12 27 49 PM 7 10 20 12 27 49 PM...

Page 34: ...180 210 240 300C 1 2 3 4 5 6 7 TXV 8 9 4 2 8 5 7 9 6 3 3 3 1 2 UATQ120 150 180 210 240 300C a UATQ180 210C 9 b 0 IM 5RTC 0315 6 DAIKIN AR indd5 5 0 IM 5RTC 0315 6 DAIKIN AR indd5 5 7 10 20 12 27 49 PM...

Page 35: ...4 OFF 1 1 ON OFF OFF OXYGEN R410A 2087 5 1 GWP GWP 1 CO2 GWP 1000 0 IM 5RTC 0315 6 DAIKIN AR indd4 4 0 IM 5RTC 0315 6 DAIKIN AR indd4 4 7 10 20 12 27 49 PM 7 10 20 12 27 49 PM...

Page 36: ...0 160 C A A B C D UATQ210C 238 238 227 227 930 UATQ240C 240 240 230 230 940 1060 160 1245 1245 D C B A 1140 910 1120 2030 50 150 2110 150 160 2110 160 720 1320 70 407 1140 90 245 2430 1950 2410 A B C...

Page 37: ...1690 1988 160 1965 1390 1988 1052 1630 48 150 50 350 165 700 125 83 83 1800 94 1800 94 142 830 D C B A 994 A B C D 190 190 230 230 840 A B C D UATQ120C 145 145 150 150 590 UATQ150C 160 160 165 165 65...

Page 38: ...50 1300 770 730 A B D 94 514 144 270 50 1520 50 145 C 1112 84 84 94 1112 94 142 1520 B A D 730 770 50 50 270 184 674 1300 1280 1350 172 145 1530 508 C A B C D 82 108 108 82 380 0 IM 5RTC 0315 6 DAIKIN...

Page 39: ...0 CVR IM 5RTC 0315 6 DAIKIN AR 2 2 0 CVR IM 5RTC 0315 6 DAIKIN AR 2 2 7 10 20 10 39 29 AM 7 10 20 10 39 29 AM...

Page 40: ...0315 6 DAIKIN R08019042228F UATQ60C UATQ90C UATQ120C UATQ150C UATQ180C UATQ210C UATQ240C UATQ300C 0 CVR IM 5RTC 0315 6 DAIKIN AR 1 1 0 CVR IM 5RTC 0315 6 DAIKIN AR 1 1 7 10 20 10 39 29 AM 7 10 20 10...

Reviews: