10
Model
Power cable
(mm
2
)
Breaker
capacity (A)
Over current
protection switch (A)
Earth cable
(mm
2
)
UATQ60C
2.5
20
20
2.5
UATQ90C
4
32
32
4
UATQ120C
6
32
32
6
UATQ150C
10
40
40
10
UATQ180C
10
50
50
10
UATQ210C
16
63
63
16
UATQ240C
16
63
63
16
UATQ300C
25
80
80
25
Note:
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated
in fixed wiring in accordance with local and national legislation.
The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or
HRC fuse.
Fix the power supply wiring to control module. Connect control wiring to control terminal block through the
control box’s hole.
Earth wiring must be connected.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used in
protective tube.
•
•
•
•
•
Model: UATQ120/150/180/210/240/300C
Control wire
Terminal
block
Power cable
CONTROL
BOX
(2) Wiring connection to unit
Route the power supply wires and control wire through the holes in the unit.
Remove the service panels and connect the units power supply wires to terminal block inside the control box, as
shown.
Make use of push releasable cable ties which are located at the bottom of control box to hold the power supply
wires properly
•
•
•
Control Module
(3) Wiring Example And Selection Of Circuit Breaker
Note:
While installing the circuit breaker onto the unit, make sure that the screws do not damage the components
(e.g. coil) inside the unit.
•
Model: UATQ60/90C
Control wire
Power cable
CONTROL BOX
Terminal block
Control
Module