background image

4

!

 WARNING

!

 CAUTION

 Installation and maintenance should be performed by 
qualified persons who are familiar with local code 
and  regulation, and experienced with this type of 
appliance.
 All field wiring must be installed in accordance with 
the national wiring regulation.
 Ensure that the rated voltage of the unit corresponds to 
that of the name plate before commencing wiring work 
according to the wiring diagram.
 The unit must be GROUNDED to prevent possible 
hazard due to insulation failure.
 All electrical wiring must not touch the refrigerant 
piping, or any moving parts of the fan motors.
 Confirm that the unit has been switched OFF before 
installing or servicing the unit.
 Disconnect from the main power supply before servicing 
the air conditioner unit.
 DO NOT pull out the power cord when the power is 
ON. This may cause serious electrical shocks which 
may result in fire hazards.
 Keep the indoor and outdoor units, power cable and 
transmission wiring, at least 1m from TVs and radios, 
to prevent distorted pictures and static. {Depending on 
the type and source of the electrical waves, static may 
be heard even when more than 1m away}.

Please take note of the following important points 
when installing.

Do not install the unit where leakage of flammable 
gas may occur.

 

If gas leaks and accumulates around the unit, it 
may cause fire ignition.

Ensure that drainage piping is connected 
properly.

 

If the drainage piping is not connected properly, 
it may cause water leakage which will dampen 
the furniture.

Do not overcharge the unit.

 

This unit is factory pre-charged. 

 

Overcharge will cause over-current or damage 
to the compressor.

Ensure that the unit’s panel is closed after service 
or installation.

 

Unsecured panels will cause the unit to operate 
noisily.

Sharp edges and coil surfaces are potential 
locations which may cause injury hazards.

  Avoid from being in contact with these places.

Before turning off the power supply, set the remote 
controller’s ON/OFF switch to the “OFF” position 
to prevent the nuisance tripping of the unit.

 If 

this is not done, the unit’s fans will start turning 
automatically when power resumes, posing a hazard 
to service personnel or the user.

Do not operate any heating apparatus too close to 
the air conditioner unit.

 

Don’t use joined and twisted wires for incoming 
power supply.
The equipment is not intended for use in a 
potentially explosive atmosphere.
Used only NITROGEN for air tight test.
Strictly do not charge OXYGEN or ACETYLENE 
into the unit for any purpose.


IMPORTANT

Important information regarding the refrigerant 
used

This product contains fluorinated greenhouse gases. Do 
not vent gases into the atmosphere.
Refrigerant type:  R410A
GWP 

(1) 

value: 2087.5

(1)

 GWP = global warming potential

The refrigerant quantity is indicated on the unit name 
plate.
Periodical inspections for refrigerant leaks may be required 
depending on European or local legislation. Please contact 
your local dealer for more information.

NOTICE

In Europe, the 

greenhouse gas emissions

 of the total 

refrigerant charge in the system (expressed as tonnes 
CO

2

-equivalent) is used to determine the maintenance  

intervals. Follow the applicable legislation.

Formula to calculate the greenhouse gas emissions:

 

GWP value of the refrigerant × Total refrigerant charge 
[in kg] / 1000

INSTALLATION MANUAL

This manual provides the procedures of installation to ensure a safe and good standard of operation for the air 
conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for 
commercial use by lay persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental 
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning 
use of the appliance by a person responsible for their safety. 
Children should be supervised to ensure that they do not play with the appliance.

NOTICE

Disposal Requirement

Dismantling of the unit, treatment of the refrigerant, oil and other parts must be done in accordance with the applicable 
legislation.

SAFETY PRECAUTIONS

1-IM-5RTC-0315(6)-DAIKIN-EN.indd4   4

1-IM-5RTC-0315(6)-DAIKIN-EN.indd4   4

7/10/20   10:35:11 AM

7/10/20   10:35:11 AM

Summary of Contents for UATQ60C

Page 1: ...Air Conditioner English Model UATQ60C UATQ90C UATQ120C UATQ150C UATQ180C UATQ210C UATQ240C UATQ300C IM 5RTC 0315 6 DAIKIN Part No R08019042228F 1 CVR IM 5RTC 0315 6 DAIKIN_EN 1 1 1 CVR IM 5RTC 0315 6...

Page 2: ...1 CVR IM 5RTC 0315 6 DAIKIN_EN 2 2 1 CVR IM 5RTC 0315 6 DAIKIN_EN 2 2 7 10 20 10 40 17 AM 7 10 20 10 40 17 AM...

Page 3: ...75 350 Weight of corner kg Total weight kg A B C D 82 108 108 82 380 84 84 1112 1112 94 142 1530 508 172 1280 1150 1300 770 730 A B D 1112 84 84 94 1112 94 142 1520 B A D 730 770 50 50 270 184 674 130...

Page 4: ...160 165 165 650 Weight at corner kg Total weight kg A B C D 190 190 230 230 840 1965 1390 1988 1052 1630 48 150 50 350 165 700 125 83 83 1800 94 1800 94 142 830 D C B A 994 1045 994 B C D A 1905 48 1...

Page 5: ...30 50 150 2110 150 160 2110 160 720 1320 70 407 1140 90 245 2430 1950 2410 English Model UATQ210 240C Model Weight at corner kg Total weight kg A B C D UATQ210C 238 238 227 227 930 UATQ240C 240 240 23...

Page 6: ...power resumes posing a hazard to service personnel or the user Do not operate any heating apparatus too close to the air conditioner unit Don t use joined and twisted wires for incoming power supply...

Page 7: ...5 7 9 6 3 3 3 1 No Item Description 1 Compressor 2 High Pressure Switch 3 Access Valve 4 Outdoor Heat Exchanger 5 Indoor Heat Exchanger 6 Filter Dryer 7 Thermal Expansion Valve TXV 8 Low Pressure Swit...

Page 8: ...OLYBAG REMOVE TOP WOODEN CRATE REMOVE ALL CARTON BOARDS FASTEN SCREWS BACK ON PANEL 4 CORNERS REMOVE BOTTOM WOODEN CRATE 1 2 3 4 5 6 Model UATQ60 90 120 150 180 210 240 300C 1 IM 5RTC 0315 6 DAIKIN EN...

Page 9: ...ral public B Duct Construction This unit are equipped with supply and return air openings Duct connection to the unit should be made with duct flanges and secured directly to the air openings with fle...

Page 10: ...no leakage and that the water drains off properly 3000 1200 1200 Evaporator coil motor service Air filter service 1200 Condenser air inlet The drain piping should have a drain trap Drain piping The d...

Page 11: ...60 3304 3587 3776 4248 Condenser air flow CFM 5100 7500 9900 13800 12230 21500 22000 L s 2407 3540 4672 6513 5772 10147 10383 Control Sequential Controller Compressor Type Quantity Scroll 1 Scroll 2 A...

Page 12: ...ord must be equivalent to H07RN F which is the minimum requirement and to be used in protective tube Model UATQ120 150 180 210 240 300C Control wire Terminal block Power cable CONTROL BOX 2 Wiring con...

Page 13: ...re to perform curling Problems with the work may cause heat and fires Stripping wire at terminal block Good Wrong Strip wire end to this point Excessive strip length may cause electrical shock or leak...

Page 14: ...ith condition 29 C DB 19 C WB indoor 46 C DB outdoor All the additional capacitor has to be field supplied based on the suggested capacitor size in table to achieve 0 9F All calculations subjected to...

Page 15: ...Pressure Pascal 50 85 150 200 250 RPM PO kW RPM PO kW RPM PO kW RPM PO kW RPM PO kW 3300 579 0 46 667 0 59 797 0 79 894 0 97 984 1 17 4400 657 0 85 728 1 00 834 1 25 918 1 46 998 1 68 5300 729 1 29 78...

Page 16: ...Cubic feet per minute PO Motor power output Airflow rate CFM External Static Pressure Pascal 50 100 165 200 250 RPM PO kW RPM PO kW RPM PO kW RPM PO kW RPM PO kW 5800 546 0 97 623 1 21 720 1 54 767 1...

Page 17: ...se phase Switch off the unit Check the 3 phase wiring T phase missing Switch off the unit Check the 3 phase wiring S phase missing Switch off the unit Check the 3 phase wiring R phase missing Switch o...

Page 18: ...r some simple troubleshooting tips Problem Causes Action Unit does not run Power failure Press the ON OFF after power restore Fuse blown or circuit breaker tripped Replace fuse or reset circuit breake...

Page 19: ...1 CVR IM 5RTC 0315 6 DAIKIN_EN 3 3 1 CVR IM 5RTC 0315 6 DAIKIN_EN 3 3 7 10 20 10 40 17 AM 7 10 20 10 40 17 AM...

Page 20: ...aikinmea com Zandvoordestraat 300 B 8400 Oostende Belgium Importer for Turkey Allianz Plaza Kucukbakkalkoy Mah Kay sdagi Cad No 1 34750 Atasehir ISTANBUL TURKIYE Head office Umeda Center Bldg 2 4 12 N...

Page 21: ...URKIYE Head office Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global Lot 6...

Page 22: ...0 CVR IM 5RTC 0315 6 DAIKIN AR 3 3 0 CVR IM 5RTC 0315 6 DAIKIN AR 3 3 7 10 20 10 39 29 AM 7 10 20 10 39 29 AM...

Page 23: ...16 40 2 ON OFF 3 3 UATQ210 240C 0 IM 5RTC 0315 6 DAIKIN AR indd16 16 0 IM 5RTC 0315 6 DAIKIN AR indd16 16 7 10 20 12 27 41 PM 7 10 20 12 27 41 PM...

Page 24: ...PW P_R P_S P_T 3 T 3 S 3 R 3 T S 3 PP01 1 81 71 LED R 2 UATQ60 90C LED PW P_S P_T 3 T 3 S 3 R 3 UATQ120 150 180 210 240 300C 0 IM 5RTC 0315 6 DAIKIN AR indd15 15 0 IM 5RTC 0315 6 DAIKIN AR indd15 15 7...

Page 25: ...77 1046 5 16 1092 5 55 10750 952 5 32 50 100 165 200 250 RPM PO kW RPM PO kW RPM PO kW RPM PO kW RPM PO kW 5800 546 0 97 623 1 21 720 1 54 767 1 72 835 1 99 7600 618 1 71 679 2 00 758 2 41 798 2 62 8...

Page 26: ...5 1 10 1607 1 21 1687 1 31 1766 1 42 2800 3300 50 85 150 200 250 RPM PO kW RPM PO kW RPM PO kW RPM PO kW RPM PO kW 3300 579 0 46 667 0 59 797 0 79 894 0 97 984 1 17 4400 657 0 85 728 1 00 834 1 25 918...

Page 27: ...UATQ120C 10 UATQ150C 20 UATQ180C 20 UATQ210C 25 UATQ240C 30 UATQ300C 30 19 29 ISO 46 0 9 b UATQ60 90 UATQ120 150 180 UATQ210 240 300 0 IM 5RTC 0315 6 DAIKIN AR indd12 12 0 IM 5RTC 0315 6 DAIKIN AR ind...

Page 28: ...7 4 a 4 3 6 4 5 1 1 2 4 4 7 UATQ120 150 180C UATQ210 240 300C 1 1 4 1 4 7 6 5 3 4 4 4 2 3 6 4 7 5 1 1 1 4 1 4 4 1 0 IM 5RTC 0315 6 DAIKIN AR indd11 11 0 IM 5RTC 0315 6 DAIKIN AR indd11 11 7 10 20 12...

Page 29: ...UATQ150C 10 40 40 10 UATQ180C 10 50 50 10 UATQ210C 16 63 63 16 UATQ240C 16 63 63 16 UATQ300C 25 80 80 25 HRC H07RN F UATQ120 150 180 210 240 300C UATQ60 90C 0 IM 5RTC 0315 6 DAIKIN AR indd10 10 0 IM 5...

Page 30: ...0 x 4 895 x 685 x 4 834 x 760 x 4 1040 x 750 x 4 1040 x 1050 x 4 UATQ60C UATQ90C UATQ120C UATQ150C UATQ180C UATQ210C UATQ240C UATQ300C V Ph Hz 380 415 3N 50 Comp A 15 20 15 15 19 19 20 20 23 23 25 25...

Page 31: ...1 A 3000 1200 1200 1200 A B C mmAq ESP 70 A 2C B 2 X ESP C 1200 1200 1200 3000 UAT60 90C UATQ120 150 180 210 240 300C 0 IM 5RTC 0315 6 DAIKIN AR indd8 8 0 IM 5RTC 0315 6 DAIKIN AR indd8 8 7 10 20 12...

Page 32: ...7 A B C 4 4 UATQ210 240C 2000 4 0 IM 5RTC 0315 6 DAIKIN AR indd7 7 0 IM 5RTC 0315 6 DAIKIN AR indd7 7 7 10 20 12 27 49 PM 7 10 20 12 27 49 PM...

Page 33: ...6 UATQ60 90 120 150 180 210 240 300C 4 1 2 3 4 5 6 0 IM 5RTC 0315 6 DAIKIN AR indd6 6 0 IM 5RTC 0315 6 DAIKIN AR indd6 6 7 10 20 12 27 49 PM 7 10 20 12 27 49 PM...

Page 34: ...180 210 240 300C 1 2 3 4 5 6 7 TXV 8 9 4 2 8 5 7 9 6 3 3 3 1 2 UATQ120 150 180 210 240 300C a UATQ180 210C 9 b 0 IM 5RTC 0315 6 DAIKIN AR indd5 5 0 IM 5RTC 0315 6 DAIKIN AR indd5 5 7 10 20 12 27 49 PM...

Page 35: ...4 OFF 1 1 ON OFF OFF OXYGEN R410A 2087 5 1 GWP GWP 1 CO2 GWP 1000 0 IM 5RTC 0315 6 DAIKIN AR indd4 4 0 IM 5RTC 0315 6 DAIKIN AR indd4 4 7 10 20 12 27 49 PM 7 10 20 12 27 49 PM...

Page 36: ...0 160 C A A B C D UATQ210C 238 238 227 227 930 UATQ240C 240 240 230 230 940 1060 160 1245 1245 D C B A 1140 910 1120 2030 50 150 2110 150 160 2110 160 720 1320 70 407 1140 90 245 2430 1950 2410 A B C...

Page 37: ...1690 1988 160 1965 1390 1988 1052 1630 48 150 50 350 165 700 125 83 83 1800 94 1800 94 142 830 D C B A 994 A B C D 190 190 230 230 840 A B C D UATQ120C 145 145 150 150 590 UATQ150C 160 160 165 165 65...

Page 38: ...50 1300 770 730 A B D 94 514 144 270 50 1520 50 145 C 1112 84 84 94 1112 94 142 1520 B A D 730 770 50 50 270 184 674 1300 1280 1350 172 145 1530 508 C A B C D 82 108 108 82 380 0 IM 5RTC 0315 6 DAIKIN...

Page 39: ...0 CVR IM 5RTC 0315 6 DAIKIN AR 2 2 0 CVR IM 5RTC 0315 6 DAIKIN AR 2 2 7 10 20 10 39 29 AM 7 10 20 10 39 29 AM...

Page 40: ...0315 6 DAIKIN R08019042228F UATQ60C UATQ90C UATQ120C UATQ150C UATQ180C UATQ210C UATQ240C UATQ300C 0 CVR IM 5RTC 0315 6 DAIKIN AR 1 1 0 CVR IM 5RTC 0315 6 DAIKIN AR 1 1 7 10 20 10 39 29 AM 7 10 20 10...

Reviews: