Si-93
Troubleshooting
Troubleshooting
49
1.19
Damper Motor
Error Detection
Method
Check damper motor and limit switch when damper motor does not operate.
Error Generating
Conditions
Possible Causes
Troubleshooting
Check resistance and voltage — DAMPER MOTOR
NO
YES
YES
Is
measured
value 0
Ω
when limit switch
turns on, and
infinity when
it turns
off?
Damper motor is
normal.
Place tester probes
at connectors of limit
switch, and check
continuity while
moving switch by
hand.
Limit switch is faulty.
Damper motor is faulty.
(HF017)
NO
Is
measured
value of EJ type
approx. 17 k
Ω
?
Place tester probes
on connectors of
damper motor and
check resistance.
(HL038)
Summary of Contents for VAM 1000EJ
Page 5: ...Si 93 iv Table of Contents ...
Page 7: ...Introduction Si 93 vi 1 1 1 Cautions in Repair Warning ...
Page 8: ...Si 93 Introduction vii ...
Page 11: ...Si 93 2 General Constructions ...
Page 15: ...Si 93 6 Operation ...
Page 21: ...Si 93 12 Maintenance ...
Page 27: ...Si 93 18 Control Functions ...
Page 35: ...Si 93 26 Circuit Operations ...
Page 39: ...Si 93 30 Troubleshooting ...
Page 59: ...Troubleshooting Si 93 50 Troubleshooting ...
Page 61: ...Si 93 52 Supplementary Explanation ...
Page 72: ...Si 93 Appendix 63 Part 8 Appendix 1 Appendix 65 1 1 Wiring Diagram 65 ...
Page 73: ...Si 93 64 Appendix ...
Page 74: ...Si 93 Appendix Appendix 65 1 Appendix 1 1 Wiring Diagram VAM500EJVE VAM800EJVE VAM1000EJVE ...
Page 75: ...Appendix Si 93 66 Appendix VAM2000EJVE ...
Page 79: ...Si 93 iv Index ...