Si-93
Control Functions
Control Functions
21
1.2.2
Pre-cool/Pre-heat
Pre-cool/pre-heat operations require the following conditions.
1. System
Pre-heat operation is possible only in air conditioner linked system (1 group, 2-group link). Check the
system first.
2. Heat reclaim ventilation setting
Set Preheat ON/OFF to ON.
Pre-cool/pre-heat On/OFF setting can be made in air conditioner or using field setting mode of LCD
remote controller of heat reclaim ventilation unit. (Pre-cool time can be set between 30 and 60 min, and
pre-heat time can be set between 30 and 150 min.)
3. Others
a) Heat reclaim ventilation unit must be in non-operating condition for two consecutive hours or more
prior to pre-cool/pre-heat operation.
b) Temperature control mode of the air conditioner must be set to Cool, Heat or Dry.
Note:
Operation standby indication is displayed only on LCD remote controller of heat reclaim ventilation unit.
Operation
Normal ventilation
mode selection
Pre-cool/pre-heat
time over
Stop
Air conditioner
ON/OFF
Operation
Heat reclaim
v
entilation unit
Ventilation fan motor
Damper motor
(ventilation mode)
Pre-cool/pre-heat ventilation
ON
ON
Total heat exchange ventilation
Normal ventilation
Total heat
exchange
ventilation
Remote controller
indication
Operation lamp
Lamp
ON
Lamp
ON
Operation standby
indication
(HL022)
Summary of Contents for VAM 1000EJ
Page 5: ...Si 93 iv Table of Contents ...
Page 7: ...Introduction Si 93 vi 1 1 1 Cautions in Repair Warning ...
Page 8: ...Si 93 Introduction vii ...
Page 11: ...Si 93 2 General Constructions ...
Page 15: ...Si 93 6 Operation ...
Page 21: ...Si 93 12 Maintenance ...
Page 27: ...Si 93 18 Control Functions ...
Page 35: ...Si 93 26 Circuit Operations ...
Page 39: ...Si 93 30 Troubleshooting ...
Page 59: ...Troubleshooting Si 93 50 Troubleshooting ...
Page 61: ...Si 93 52 Supplementary Explanation ...
Page 72: ...Si 93 Appendix 63 Part 8 Appendix 1 Appendix 65 1 1 Wiring Diagram 65 ...
Page 73: ...Si 93 64 Appendix ...
Page 74: ...Si 93 Appendix Appendix 65 1 Appendix 1 1 Wiring Diagram VAM500EJVE VAM800EJVE VAM1000EJVE ...
Page 75: ...Appendix Si 93 66 Appendix VAM2000EJVE ...
Page 79: ...Si 93 iv Index ...