Si71-502
Troubleshooting
Operation Manual
91
• If the display “
” (INSPECTION), “UNIT No.” and the OPERATION lamp flash and the
“MALFUNCTION CODE” appears.
Measure:
Notify and inform the model name and what the malfunction code indicates to your Daikin
dealer.
• There are other malfunctions.
Measure:
Stop the unit.
List of malfunction codes of Remote controller of the HRV-system
In case of the malfunction with the code in white letters on the black background in the unit still
operates.
However, be sure to have it inspected and repaired and as soon as possible.
If other than the above error codes are displayed, there is a possibility that the problem in question
has occurred with a combined air conditioner or outdoor unit. See the operation manuals included
with the air conditioners or outdoor units for details.
5.3
If the System does not Properly Operate Except for the above Mentioned
Case, and None of the above Mentioned Malfunctions is Evident, Investigate
the System According to the Following Procedures.
1. The unit does not operate at all.
• Check if there is a power failure.
After power has been restored, start operation again.
• Check if the fuse has blown or breaker has worked.
Change the fuse or set the breaker.
2. Amount of discharged air is small and the discharging sound is high.
• Check if the air filter and heat exchange element are clogged.
Clean tha air filter and heat exchange element.
3. Amount of discharged air is large and so is the sound.
• Check if the air filter and heat exchange element are not installed.
Install the air filter and heat exchange element.
Operation
lamp
Inspection
indicator
Unit No.
Malfunction
code
Description
On
Off
Blinking
64
Indoor air thermistor malfunction
On
Off
Blinking
65
Outdoor air thermistor malfunction
On
Off
Blinking
6A
Dumper-related malfunction
Blinking
Blinking
Blinking
6A
Dumper-related malfu thermistor
malfunction
Blinking
Blinking
Blinking
U5
Transmission error between the unit and remote
controller
Off
Blinking
Off
U5
Setting error of remote controller
Off
Blinking
Off
U8
Transmission error between main remote
controller and sub remote controller
Off
Blinking
Blinking
UA
Incorrect combination with indoor unit and remote
controller.
On
Blinking
On
UC
Central control address over lapping
Blinking
Blinking
Blinking
UE
Transmission error between the unit and
centralized controller
T
UNIT No.
INSPECTION
display
MALFUNCTION CODE
INDOOR UNIT No. in which
a malfunction occurs
OPERATION lamp
Summary of Contents for VAM 350GJVE
Page 7: ...Introduction Si71 502 vi 1 1 1 Cautions in Operation and Maintenance...
Page 8: ...Si71 502 Introduction vii...
Page 13: ...General Constructions Si71 502 4 General Constructions...
Page 29: ...Maintenance Si71 502 20 Maintenance...
Page 43: ...Circuit Operations Si71 502 34 Circuit Operations...
Page 103: ...After sales Service Si71 502 94 Operation Manual...
Page 106: ...Si71 502 Appendix Appendix 97 VAM1500GJVE VAM2000GJVE...
Page 107: ...Appendix Si71 502 98 Appendix...