Troubleshooting
Si71-502
50
Troubleshooting
1.15
Dedicated LCD Remote Controller
When no indication is displayed on remote controller
Error Detection
Method
Check to see if remote controller displays indication.
Error Generating
Conditions
Possible Causes
Troubleshooting
Check 1, 2, 3 : Refer to page 51
Disconnect remote
controller cable from
both main unit
terminal board and
remote controller
terminal board.
Using tester, check
continuity between
two wires in cable.
Is
measured
value
∞
M
Ω
(infinity)?
NO
YES
With remote
controller cable
disconnected from
main unit PCB, check
voltage between P1
and P2 on main unit
terminal board.
Is
measured
value approx. 16
VDC?
NO
YES
Connect remote
controller cable to
main unit PCB, and
disconnect remote
controller. Check
voltage at the end of
cable on remote
control side.
Is
measured
value approx. 16
VDC?
NO
YES
There may be shorting in
remote controller cable.
Main unit PCB may be
faulty.
There may be open circuit
in remote controller cable.
Remote control PCB may
be faulty.
(HF014)
Check 1
Check 2
Check 3
Summary of Contents for VAM 350GJVE
Page 7: ...Introduction Si71 502 vi 1 1 1 Cautions in Operation and Maintenance...
Page 8: ...Si71 502 Introduction vii...
Page 13: ...General Constructions Si71 502 4 General Constructions...
Page 29: ...Maintenance Si71 502 20 Maintenance...
Page 43: ...Circuit Operations Si71 502 34 Circuit Operations...
Page 103: ...After sales Service Si71 502 94 Operation Manual...
Page 106: ...Si71 502 Appendix Appendix 97 VAM1500GJVE VAM2000GJVE...
Page 107: ...Appendix Si71 502 98 Appendix...