Troubleshooting
Si71-502
40
Troubleshooting
1.5
Outdoor Air Thermistor Error
Remote Controller
LCD Display
Error Code
65
Inspection OFF Unit No. Blinking
LED Indication
Remote Controller
4
Main Unit
5
Error Detection
Method
Temperature detected by outside air temperature sensor is used to detect errors.
Error Generating
Conditions
When value detected by outside air temperature sensor is -40ºC or below (open circuit) or 70ºC or higher
(short-circuit).
Possible Causes
Faulty sensor
Broken wire
Faulty control PCB
Faulty contact in connector
Troubleshooting
Note:
Note 1:
Refer to the thermistor temperature - resistance conversion table when measuring resistance.
Thermistor temperature - resistance conversion table
If measured value deviates significantly from above values, thermistor is faulty.
Use tester to check resistance
Remove outdoor air
thermistor (R2T) from
X13A (2P) on control
PCB, and measure
resistance.
Is
thermistor
normal?
Note 1
YES
NO
Replace outdoor
air thermistor.
If there is no faulty
contact, replace
control PCB.
(HF004)
Thermistor
temperature
Sensor resistance
Thermistor
temperature
Sensor resistance
-10ºC or less
108k
Ω
or more
22ºC
Approx. 23k
Ω
-5ºC
Approx. 85k
Ω
24ºC
Approx. 21k
Ω
0ºC
Approx. 66k
Ω
26ºC
Approx. 19k
Ω
5ºC
Approx. 51k
Ω
28ºC
Approx. 18k
Ω
10ºC
Approx. 40k
Ω
30ºC
Approx. 16k
Ω
14ºC
Approx. 33k
Ω
35ºC
Approx. 13k
Ω
16ºC
Approx. 30k
Ω
40ºC
Approx. 11k
Ω
18ºC
Approx. 27k
Ω
50ºC or more
7k
Ω
or less
20ºC
Approx. 25k
Ω
Continuity check
(HL028)
Summary of Contents for VAM 350GJVE
Page 7: ...Introduction Si71 502 vi 1 1 1 Cautions in Operation and Maintenance...
Page 8: ...Si71 502 Introduction vii...
Page 13: ...General Constructions Si71 502 4 General Constructions...
Page 29: ...Maintenance Si71 502 20 Maintenance...
Page 43: ...Circuit Operations Si71 502 34 Circuit Operations...
Page 103: ...After sales Service Si71 502 94 Operation Manual...
Page 106: ...Si71 502 Appendix Appendix 97 VAM1500GJVE VAM2000GJVE...
Page 107: ...Appendix Si71 502 98 Appendix...