Si71-502
Troubleshooting
Troubleshooting
43
1.8
Dedicated LCD Remote Controller
When “
88
” remains on remote controller display.
Error Detection
Method
When “
88
” remains on remote controller display.
Error Generating
Conditions
Possible Causes
Master-slave setting of remote controller
Remote controller PCB assembly error
Main unit PCB assembly error
Troubleshooting
Dedicated Remote Controller
Main Unit PCB
Check to see if master-
slave remote controller is
used.
Check microcomputer
operation monitor on
main unit PCB.
Is it flashing?
YES
YES
Change master-slave selection
switch to set proper master-
slave relation.
One should be set to Master,
and the other set to Slave.
Replace remote controller.
Replace main unit PCB.
Is
master-slave
remote controller
used?
(HF007)
NO
NO
Master-slave
selection switch
Remote controller
PCB assembly
(HL030)
Exhaust
air fan
Supply
air fan
CN3
CN4
CN2
CN1
CN7
FuL
10A
CN13
CN8
CN12
CN5
CN6
CN9
KRP
50-2
CN11
CN10
L
N
P2
P1
F1
F2
J1
J2
JC
LED A
(HL031)
(Microcomputor Operation Monitor)
Summary of Contents for VAM 350GJVE
Page 7: ...Introduction Si71 502 vi 1 1 1 Cautions in Operation and Maintenance...
Page 8: ...Si71 502 Introduction vii...
Page 13: ...General Constructions Si71 502 4 General Constructions...
Page 29: ...Maintenance Si71 502 20 Maintenance...
Page 43: ...Circuit Operations Si71 502 34 Circuit Operations...
Page 103: ...After sales Service Si71 502 94 Operation Manual...
Page 106: ...Si71 502 Appendix Appendix 97 VAM1500GJVE VAM2000GJVE...
Page 107: ...Appendix Si71 502 98 Appendix...