Troubleshooting
Troubleshooting
47
1.12
Field Setting Error
Remote Controller
LCD Display
Error Code
UA
Inspection Blinking Unit No. OFF
LED Indication
Remote Controller
1
Main Unit
5
Error Detection
Method
Error Generating
Conditions
Possible Causes
Faulty combination of remote controller
More than 16 units connected to remote controller cable.
Faulty remote controller
Troubleshooting
<Combination-Right or Wrong>
Main body
Remote controller
Right/Wrong
Heat reclaim ventilation unit only
Heat reclaim ventilation unit
Right
Heat reclaim ventilation unit only
Air conditioner
Right
Heat reclaim ventilation unit + air-conditioner
Heat reclaim ventilation unit
Wrong
Heat reclaim ventilation unit + air-conditioner
Air-conditioner
Right
YES
YES
Check the system, and correct
connections.
Change connections so that 16
or fewer units are connected to
remote controller cable.
Replace remote controller.
Is
combination
of remote
controller and heat
reclaim ventilation
unit (air
conditioner)
correct?
NO
(HF011)
Are
17 or more
units connected
to remote
controller
cable?
NO
Refer "Combination-Right or Wrong"
Summary of Contents for VAM 350GJVE
Page 7: ...Introduction Si71 502 vi 1 1 1 Cautions in Operation and Maintenance...
Page 8: ...Si71 502 Introduction vii...
Page 13: ...General Constructions Si71 502 4 General Constructions...
Page 29: ...Maintenance Si71 502 20 Maintenance...
Page 43: ...Circuit Operations Si71 502 34 Circuit Operations...
Page 103: ...After sales Service Si71 502 94 Operation Manual...
Page 106: ...Si71 502 Appendix Appendix 97 VAM1500GJVE VAM2000GJVE...
Page 107: ...Appendix Si71 502 98 Appendix...