Overlapping Central Control Address
Remote Controller
LCD Display
Error Code
UUU
UCCCC
Inspection
4
Unit No.
4
LED Indication
Remote Controller
4
Main Unit
5
Error Detection
Method
Remote controller microcomputer checks for double-setting of addresses.
Error Generating
Conditions
When same address is set to two or more units.
Possible Causes
■
Overlapping of central control address
■
Faulty remote control
Troubleshooting
Change central
control address
settings using remote
controller.
Then, turn off power,
and restart.
Does
equipment reset
properly?
YES
Replace remote controller.
End of correction procedure.
(HF012)
NO