Supplementary Explanation
Si-93
54
Supplementary Explanation
Centralized control
group No. setting
(Mode No. 00)
Setting of
Individual No.
(Mode No. 30)
Field setting mode
Mode No.
Group No.
3
4
1, 5
(HL040)
2
Step 1
With equipment in normal mode, press the
button for more than 4 seconds to enter field
setting mode.
Step 2
Mode No.: UP
↔
Mode No.: DOWN
Use [MODE] and [AIR VOLUME] to select mode No.00 (30).
Step 3
Press
or
button to select Group No.
Step 4
Press
button once to enter settings.
Step 5
Press
button to return to normal mode.