14 Commissioning

Installation and operation manual

25

VAM350~2000J8VEB
Heat reclaim ventilation unit
4P664011-1 – 2021.08

TEST

FRESH UP

1

2

8

4
3

9

10

13

12

11

6

1

Operation lamp

This red pilot lamp lights up while the unit is in operation.

2

Operation/Stop button

Press this button once and the unit starts to operate. Press this
button again and the unit stops.

3

Air flow rate changeover button

Use this button to change the air flow to " " Low, "

" High, "

FRESH  UP"  Low  Fresh-up,  or  "

  FRESH  UP"  High  Fresh-up

mode.

When this indication does NOT show, the volume of outdoor air
supplied  into  the  room  and  that  of  the  room  air  exhausted
outdoors is equal.

For "FRESH UP" operation

▪ If  the  Fresh-up  setting  is  set  to  "Fresh  up  air  supply":  The

volume of outdoor air supplied into the room is larger than that
of  room  air  exhausted  outdoors.  This  prevents  odours  and
moisture  from  kitchens  and  toilets  from  flowing  into  the  room.
This is the factory setting.

▪ If  the  Fresh-up  setting  is  set  to  "Fresh  up  air  exhaust":  The

volume  of  room  air  exhausted  outdoors  is  larger  than  that  of
outdoor  air  supplied  into  the  room.  This  prevents  hospital
odours  and  airborne  micro-organisms  from  flowing  out  of  the
room into the corridors.

To  change  this  setting,  see  List  of  settings  in  the  installer  and
user reference guide.

4

Ventilation mode changeover button:

"

A

(

(

" Automatic mode

The  unit's  temperature  sensor  automatically  changes  the
operation  mode  of  the  unit  to  Bypass  mode  or  Heat  Reclaim
Ventilation mode.

"

" Heat Reclaim Ventilation mode

In this mode, the outdoor air passes through the heat exchange
element to effect Heat Reclaim Ventilation.

"

" Bypass mode

In  this  mode,  the  outdoor  air  does  NOT  pass  through  the  heat
exchange element, but bypasses it to effect Bypass ventilation.

5

Indication of operation control method: 

When operation of the heat reclaim ventilation units is linked to
the air conditioners, this indication may be displayed. While this
indication  is  displayed,  the  heat  reclaim  ventilation  units
CANNOT  be  turned  on  or  off  with  the  controller  of  the  heat
reclaim ventilation units.

6

Indication of operation standby: 

This  icon  indicates  that  the  unit  is  precooling/preheating.  The
unit's start-up is delayed until precooling/preheating is finished.

Precooling/preheating  means  that  the  heat  reclaim  ventilation
units  are  NOT  started  while  linked  air  conditioners  are  starting
up, for example, before office hours.

During  this  period,  the  cooling  or  heating  load  is  reduced  to
bring  the  room  temperature  to  the  set  temperature  in  a  short
time.

7

Indication of central control: 

When  a  controller  for  air  conditioners  or  devices  for  central
control  are  connected  to  the  heat  reclaim  ventilation  units,  this
icon may be displayed.

While this indication is displayed, you may NOT be able to turn
the  heat  reclaim  ventilation  units  on  or  off,  or  use  the  timer
function with the controller of the heat reclaim ventilation unit.

8

Indication of air filter cleaning

When the display shows "

", clean the air filter.

9

Filter signal reset button

10

Inspection button

Use this button ONLY when servicing the unit.

11

Schedule timer button: 

/

This button enables or disables the schedule timer.

12

Time adjust button: 

13

Programming button: 

/

To set the timer

1

Press the schedule timer button.

2

Press the time adjust button to set the time.

3

Press the programming button to save the setting.

13.4.3

BRC1H controller

INFORMATION

Please refer to the Installer and user reference guide of the
BRC1H user interface.

14

Commissioning

14.1

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit MUST be closed. Power-up the
unit after it is closed.

You  read  the  complete  installation  and  operation
instructions,  as  described  in  the 

installer  and  user

reference guide

.

Summary of Contents for VAM-J8 Series

Page 1: ...n and operation manual Heat reclaim ventilation unit English Installation and operation manual Heat reclaim ventilation unit VAM350J8VEB VAM500J8VEB VAM650J8VEB VAM800J8VEB VAM1000J8VEB VAM1500J8VEB V...

Page 2: ...orabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartu...

Page 3: ...troller 25 14 Commissioning 25 14 1 Checklist before commissioning 25 14 2 Checklist during commissioning 26 14 2 1 About the test run 26 15 Troubleshooting 26 15 1 Solving problems based on error cod...

Page 4: ...the applicable legislation Make electrical connections to the fixed wiring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING After fin...

Page 5: ...nd may cause accidents WARNING ALWAYS use multicore cable for power supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full...

Page 6: ...VDX In order to be effective the installed unit MUST be electrically powered at all times except for short service periods CAUTION Before accessing make sure to turn OFF the operation switch and disco...

Page 7: ...OTICE NEVER wash the heat exchange element with water NEVER touch the heat exchange element paper because it can be damaged if it is forced Do NOT crush the heat exchange element To clean the heat exc...

Page 8: ...e at all Check if there is no power failure Wait until power is restored and restart operation Check if no fuse has blown or breaker is activated Change the fuse or reset the breaker if necessary Chec...

Page 9: ...VAM unit location Temperature 0 C DB 40 C DB Relative humidity 80 It is possible that due to condensation the paper heat exchanger deteriorates when the unit operates in conditions with high indoor hu...

Page 10: ...ion is effective to reduce blowing noises When selecting installation materials consider the required volume of air flow and the acceptable level of noise for that particular installation When room ai...

Page 11: ...pter PCB KRP2A51 in the installation box KRP1BA101 4 Follow the installation instructions provided with the option kits BRP4A50A KRP2A51 and KRP1BA101 5 Guide the PCB wire through the dedicated holes...

Page 12: ...xample if 2 units are installed closely together only 1 inspection hole is required for maintaining or replacing filters heat exchange elements a b c a Control box b Service cover c Inspection hole Ke...

Page 13: ...optional EKVDX see EKVDX operation and installation manual Models 350 1000 b c a d a Name Plate Models 1500 2000 d c e e f a Aluminium tape field supply b Insulation material field supply c Duct flan...

Page 14: ...rminal Loose connections may reduce the protection For the controller wiring refer to the installation manual of the controller delivered with the controller Wiring example VRV HRV P1 P1 P1 P2 P2 P2 L...

Page 15: ...ptional controller i Power supply cable j Wires for connection of additional external damper supplied accessory k Insulated splices closed barrel connector 0 75 mm field supply l Double or reinforced...

Page 16: ...l controller Ii Power supply cable j Wires for connection of additional external damper supplied accessory k Insulated splices closed barrel connector 0 75 mm field supply l Double or reinforced insul...

Page 17: ...e VAM is switched off The VAM main PCB provides a contact for an external damper PCB X24A a b c d a VAM b External damper c External damper earthing d Power source CAUTION Follow the instructions belo...

Page 18: ...or the air conditioner The settings format e g 19 29 1 02 that are used in this chapter are composed of 3 parts divided by Mode number e g 19 29 where 19 is the mode number for group settings and 29 i...

Page 19: ...n b to select a mode number Result The code display is blinking 3 To configure settings for individual units under group control press the Timer setting on off button c and select the number of the un...

Page 20: ...29 C 30 C 8 Central zone link No Yes 9 Preheat time extension c 0 minutes 30 minutes 60 minutes 90 minutes 18 28 0 External signal g JC J2 Last command Priority on external input Priority on operation...

Page 21: ...y system n OFF ON 1A 0 Fresh up operation k OFF ON a Factory settings are marked with a grey background b In case VAM and EKVDX are combined and the R32 safety system of the VAM is active the nighttim...

Page 22: ...must be equal in order to have a balanced system Models 350 1000 Settings 19 29 2 and 19 29 3 Balance exhaust air and supply air with fan steps 1 15 based on the air flow curves see the databook and t...

Page 23: ...ting 19 29 0 04 CANNOT be configured if the outside temperature is 10 C which is out of the operation range Setting 19 29 0 05 CANNOT be configured if the outside temperature is 5 C In this case error...

Page 24: ...tdoor air is supplied to the room without heat exchange with the room air Time to clean filter indication When the filter pressure drop becomes too large the following message or icon is displayed at...

Page 25: ...on of the heat reclaim ventilation units is linked to the air conditioners this indication may be displayed While this indication is displayed the heat reclaim ventilation units CANNOT be turned on or...

Page 26: ...ion of the system turn on the power of the heat reclaim ventilation units Refer to the manual of the controller of each unit controller for air conditioner central controller etc to conduct a trial op...

Page 27: ...power supply printed circuit board Symbols Field wiring Terminals Connectors Protective earth Noiseless earth Colours BLK Black BLU Blue BRN Brown GRN Green ORG Orange RED Red WHT White YLW Yellow Tr...

Page 28: ...and operation manual 28 VAM350 2000J8VEB Heat reclaim ventilation unit 4P664011 1 2021 08 17 2 Service space 50 a 150 250 mm A B a Service space Models A B VAM350 500 900 mm 675 mm VAM650 1100 mm 700...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...4P664011 1 2021 08 Copyright 2021 Daikin 4P664011 1 0000000G Verantwortung f r Energie und Umwelt...

Reviews: