Installation Manual
EDMMT712101
132
VAM-HVE/HVLT Series
3P645058-1
10
English
6-3
Wiring
E
xamples
Examples of wiring for each system are shown below.
y
Remote controller wiring and transmission
wiring are not polarized.
Install a circuit breaker.
Failure to install a circuit breaker may result in electric shock or fire.
WARNING
For Independent System
L
N
P1
P2
L
N
P1
P2
P1
P2
P1
P2
Power supply (
Ú
1)
Power supply (
Ú
1)
Heat Reclaim Ventilator 1
Earth
Earth
Transmission
wiring up to 500m
Remote
controller
MAIN
x
Circuit breaker (for
protection against
earth fault, overload,
and short circuit)
Remote
controller
SUB
Heat Reclaim Ventilator 2
Combined operation system with air conditioner
Heat Reclaim Ventilator
Air conditioner
Indoor unit
Power supply (
Ú
1)
Earth
Earth
Transmission
wiring up to 500m
Remote
controller
MAIN
x
Circuit breaker (for
protection against
earth fault, overload,
and short circuit)
Remote
controller
SUB
L
N
P1
P2
P1
P2
P1
P2
P1
P2
For control by 2 remote controllers (Controlling 1 group by 2 remote controllers)
y
When using 2 remote controllers, one must be set to “MAIN” and the other must be set to
“secondary”.
<MAIN/SUB change over method>
Refer to the installation manual of the remote controller. (Factory default setting is “MAIN”.)
<Wiring method>
6-2
Wiring Connection
Method
Connect the SUB remote controller to the device at the end of the remote
controller wiring [P2 / P1] according to
Indoor unit
Heat Reclaim Ventilator (1)
Heat Reclaim Ventilator (2)
MAIN remote
controller
MAIN remote
controller
Remote controller wiring [P2 / P1]
P1
1
P
2
P
P2
P1
P2
For central control
x
Circuit breaker (for
protection against
earth fault, overload,
and short circuit)
Air conditioner
outdoor unit
Centralized
equipment
F 1 F 2
F 1 F 2
F 1 F 2
F 1 F 2
F 1 F 2
N
L
P1
P2
P1
P2
P1
P2
P1
P2
Remote controller
Remote controller
Power supply (
Ú
1)
Air conditioner indoor unit
IN/OUT
Heat Reclaim Ventilator
y
If control is performed with a central device (such as central controller), a
group number needs to be set with the remote controller.
See the manual of each central device for details.
y
Even when the central device is used for controls, you still use the remote
controller to change field settings. Install the remote controller in an
operable location.
For remote operations
y
Remote operation can be performed by connecting the external input
(Input A) to terminals J1, J2, and JC of the terminal block (X2M).
)
e
ri
w
2
(
e
l
b
a
c
r
o
d
r
o
c
l
y
n
i
v
d
e
h
t
a
e
h
S
e
p
y
t
e
ri
W
m
m
5
2
.
1
-
5
7
.
0
e
z
i
s
e
ri
W
2
m
0
5
.
x
a
M
h
t
g
n
e
l
e
ri
W
Specifi cations for
external contact
Contact that can open and close minimum load DC12V, 1mA
Model Name
VAM150HVE
VAM250HVE
VAM350HVE
VAM500HVE
VAM650HVE
VAM800HVE
VAM1000HVE
Power supply (
Ú
1)
1-phase 220-240/220V 50/60Hz
(1)
Fresh-up operation
Supply air volume can be set at a higher level than the exhaust air (Supply
Fresh-Up) or the other way round (Exhaust Fresh-Up) by input from an external
contact point.
y
Set the fresh-up mode to “Supply” fresh-up or “Exhaust” fresh-up on the remote
controller.
Make settings according to
FIELD SETTING AND TEST RUN
7
.
y
Connect the external input (Input A) to terminals J2 and JC of the terminal block
(X2M).
(External
contact)
Heat Reclaim Ventilator
J1 J2 J3 JC
Status of contact on-site
Operation of the unit
Input A
Short circuit
Fresh-up operation
OPEN Normal
operation
(2)
Forced OFF
y
Set the external input setting to “Forced OFF” on the remote controller.
Make settings according to
FIELD SETTING AND TEST RUN
7
.
y
Connect the external input (Input A) to terminals J2 and JC of the terminal block
(X2M).
(External
contact)
Heat Reclaim Ventilator
J1 J2 J3 JC
Status of contact on-site
Operation of the unit
Input A
Short circuit
Forced OFF (remote
controller not permitted)
OPEN Normal
operation
In case of operation combined with an external damper
The printed circuit board of the Heat Reclaim Ventilator main unit opens and closes
the no-voltage contact used for driving the damper in conjunction with the operation
of Heat Reclaim Ventilator .
Closes no-voltage contact by operation of Heat Reclaim Ventilator
Opens no-voltage contact by operation of Heat Reclaim Ventilator
y
Wiring instructions
The fan operation signal of Heat Reclaim Ventilator is output from terminals X1
and X2 of the terminal block (X3M) on the printed circuit board.
Do not use any code for the electric wire for linking with the
external damper. Example: VCTF (unusable); VV cable (usable)
A 1 P
X
X
3
1
X 2
X 3
X 4
M
Air conditioner
outdoor
Contact capacity
No-voltage contact
AC220-240V 240VA
For operation indication
Operation indication of one Heat Reclaim Ventilator will be output.
Make settings according
FIELD SETTING AND TEST RUN
7
.
y
Wiring instructions
The operation indication of Heat Reclaim Ventilator is output from terminals X3
and X4 of the terminal block (X3M) on the printed circuit board.
A 1 P
X
X
3
1
X 2
X 3
X 4
M
Power supply for indicators
1-phase 220-240/220V
Indicator
(locally procured)
Contact capacity
No-voltage contact
AC220-240V 240VA
y
Instructions on connecting transmission wiring to terminal X3M
X3M
A1 P
Bundle the lead wires with the
clamp
(accessory)
Bundle the lead wires with the
clamp
(accessory)
y
Up to 16 units of
Heat Reclaim Ventilator
can be controlled
simultaneously.
VAM150-1000HV
E
IN/OUT
③
③
Summary of Contents for VAM Series
Page 2: ......
Page 4: ...EDMMT712101 2 Table of Contents 17 6 Precautions for Design and Installation 181 ...
Page 56: ...Control System EDMMT712101 54 VAM HVE HVLT Series C 3P343420 1E ...
Page 138: ...Installation Manual EDMMT712101 136 VAM HVE HVLT Series 3P607378 3C ...
Page 139: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 137 3P607378 3C ...
Page 141: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 139 C EM20A032 ...
Page 142: ...Installation Manual EDMMT712101 140 VAM HVE HVLT Series C EM20A032 ...
Page 143: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 141 C EM20A032 ...
Page 147: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 145 3P607378 3C ...
Page 148: ...Details of Optional Accessories EDMMT712101 146 VAM HVE HVLT Series 3P607378 3C ...
Page 149: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 147 3P607378 3C ...
Page 150: ...Details of Optional Accessories EDMMT712101 148 VAM HVE HVLT Series 3P607378 3C ...
Page 151: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 149 3P607378 3C ...
Page 152: ...Details of Optional Accessories EDMMT712101 150 VAM HVE HVLT Series 3P607378 3C ...
Page 155: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 153 4P457318 1D ...
Page 156: ...Details of Optional Accessories EDMMT712101 154 VAM HVE HVLT Series 4P457318 1D ...
Page 157: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 155 4P457318 1D ...
Page 158: ...Details of Optional Accessories EDMMT712101 156 VAM HVE HVLT Series 4P457318 1D ...
Page 159: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 157 4P457318 1D ...
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......