EDMMT712101
Product Introduction
VAM-HVE/HVLT Series
19
Freezer and refrigerated
spaces (<50°F)
10
5
0
0
E
0
0
0
2
General manufacturing
(excludes heavy industrial
and processes using
chemicals)
10
5.0
0.18
0.9
7
36
18
3
Pharmacy (prep. area)
5
2.5
0.18
0.9
10
23
11.5
2
Photo studios
5
2.5
0.12
0.6
10
17
8.5
1
Shipping/receiving
10
5
0.12
0.6
B
2
70
35
2
Sorting, packing, light
assembly
7.5
3.8
0.12
0.6
7
25
12.5
2
1
—
0
.
0
0
0
.
0
—
—
s
t
e
s
o
l
c
e
n
o
h
p
e
l
e
T
Transportation waiting
7.5
3.8
0.06
0.3
H
100
8
4.1
1
Warehouses
10
5
0.06
0.3
B
—
2
Public Assembly Spaces
Auditorium seating area
5
2.5
0.06
0.3
H
150
5
2.7
1
Places of religious
worship
5
2.5
0.06
0.3
H
120
6
2.8
1
Courtrooms
5
2.5
0.06
0.3
H
70
6
2.9
1
Legislative chambers
5
2.5
0.06
0.3
H
50
6
3.1
1
Libraries
5
2.5
0.12
0.6
10
17
8.5
1
Lobbies
5
2.5
0.06
0.3
H
150
5
2.7
1
Museums (children’s)
7.5
3.8
0.12
0.6
40
11
5.3
1
Museums/galleries
7.5
3.8
0.06
0.3
H
40
9
4.6
1
Residential
Dwelling unit
5
2.5
0.06
0.3
F,G,H
F
1
Common corridors
—
—
0.06
0.3
1
H
TABLE 1 Minimum Ventilation Rates in Breathing Zone (Continued)
(This table is not valid in isolation; it must be used in conjunction with the accompanying notes.)
Occupancy
Category
People Outdoor
Air Rate
R
p
Area Outdoor
Air Rate
R
a
Notes
Default Values
Air
Class
Occupant Density
(see Note 4)
Combined Outdoor
Air Rate (see Note 5)
cfm/
person
L/s·
person
cfm/ft
2
L/s·m
2
#/1000 ft
2
or #/100 m
2
cfm/
person
L/s·person
GENERAL NOTES FOR TABLE 1
1 Relate
Values taken from ASHRAE Standard 62.1-2019
d requirements:
The rates in this table are based on all other applicable requirements of this standard being met.
2 Environmental Tobacco Smoke:
This table applies to ETS-free areas. Refer to Section 5.17 for requirements for buildings containing ETS areas and ETS-free areas.
3 Air density:
Volumetric airflow rates are based on an air density of 0.075 lb
da
/ft
3
(1.2 kg
da
/m
3
), which corresponds to dry air at a barometric pressure of 1 atm (101.3 kPa) and an
air temperature of 70°F (21°C). Rates may be adjusted for actual density but such adjustment is not required for compliance with this standard.
4 Default occupant density:
The default occupant density shall be used when actual occupant density is not known.
5 Default combined outdoor air rate (per person):
This rate is based on the default occupant density.
6 Unlisted occupancies:
If the occupancy category for a proposed space or zone is not listed, the requirements for the listed occupancy category that is most similar in terms of occupant
density, activities, and building construction shall be used.
ITEM-SPECIFIC NOTES FOR TABLE 1
A
For high-school and college libraries, use values shown for Public Assembly Spaces—Libraries.
B
Rate may not be sufficient when stored materials include those having potentially harmful emissions.
C
Rate does not allow for humidity control. Additional ventilation or dehumidification may be required to remove moisture. “Deck area” refers to the area surrounding the pool that would
be expected to be wetted during normal pool use, i.e., when the pool is occupied. Deck area that is not expected to be wetted shall be designated as a space type (for example, “spectator
area”).
D
Rate does not include special exhaust for stage effects, e.g., dry ice vapors, smoke.
E
When combustion equipment is intended to be used on the playing surface or in the space, additional dilution ventilation and/or source control shall be provided.
F
Default occupancy for dwelling units shall be two persons for studio and one-bedroom units, with one additional person for each additional bedroom.
G
Air from one residential dwelling shall not be recirculated or transferred to any other space outside of that dwelling.
H
Ventilation air for this occupancy category shall be permitted to be reduced to zero when the space is in occupied-standby mode.
Summary of Contents for VAM Series
Page 2: ......
Page 4: ...EDMMT712101 2 Table of Contents 17 6 Precautions for Design and Installation 181 ...
Page 56: ...Control System EDMMT712101 54 VAM HVE HVLT Series C 3P343420 1E ...
Page 138: ...Installation Manual EDMMT712101 136 VAM HVE HVLT Series 3P607378 3C ...
Page 139: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 137 3P607378 3C ...
Page 141: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 139 C EM20A032 ...
Page 142: ...Installation Manual EDMMT712101 140 VAM HVE HVLT Series C EM20A032 ...
Page 143: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 141 C EM20A032 ...
Page 147: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 145 3P607378 3C ...
Page 148: ...Details of Optional Accessories EDMMT712101 146 VAM HVE HVLT Series 3P607378 3C ...
Page 149: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 147 3P607378 3C ...
Page 150: ...Details of Optional Accessories EDMMT712101 148 VAM HVE HVLT Series 3P607378 3C ...
Page 151: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 149 3P607378 3C ...
Page 152: ...Details of Optional Accessories EDMMT712101 150 VAM HVE HVLT Series 3P607378 3C ...
Page 155: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 153 4P457318 1D ...
Page 156: ...Details of Optional Accessories EDMMT712101 154 VAM HVE HVLT Series 4P457318 1D ...
Page 157: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 155 4P457318 1D ...
Page 158: ...Details of Optional Accessories EDMMT712101 156 VAM HVE HVLT Series 4P457318 1D ...
Page 159: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 157 4P457318 1D ...
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......