EDMMT712101
Control System
VAM-HVE/HVLT Series
25
Setting Descriptions and Setting Numbers
Setting descriptions
Mode
No.
(Note 3)
Reset
Switch
No.
Setting position (Note 4)
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Group No. setting for centralized control
(individual)
00 (30)
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Filter contamination setting
(Filter sign display interval time setting)
17(27)
0
Approximately
2500 hours
Approximately
1250 hours
No
accumulation
—
—
—
—
—
—
—
—
—
—
—
—
Nighttime free cooling ON/OFF & start
time setting
(after the air conditioner stops)
1
OFF
ON
2 hours
later
ON
4 hours
later
ON
6 hours
later
ON
8 hours
later
—
—
—
—
—
—
—
—
—
—
Pre-cooling & pre-heating ON/OFF setting
2
OFF
ON
—
—
—
—
—
—
—
—
—
—
—
—
—
Pre-cooling & pre-heating operation time
setting
3
30 minutes
45 minutes
60 minutes
—
—
—
—
—
—
—
—
—
—
—
—
Field setting for ventilation fan
4
Normal
Ultra high
—
—
—
—
—
—
—
—
—
—
—
—
—
Setting of duct direct connection with
commercial multi air conditioners
(building multi)
5
Without duct
With duct
Without duct
With duct
—
—
—
—
—
—
—
—
—
Cold region operation setting
(Fan operation is selected when the
heating thermostat is OFF)
★
1
5
—
—
Fan OFF
Fan L
Fan OFF
Fan L
—
—
—
—
—
—
—
—
—
Airflow rate setting for nighttime free
cooling
6
High
Ultra high
—
—
—
—
—
—
—
—
—
—
—
—
—
Target temperature setting for stand-alone
nighttime free cooling
7
18˚C
19˚C
20˚C
21˚C
22˚C
23˚C
24˚C
25˚C
26˚C
27˚C
28˚C
29˚C 30˚C
—
—
Centralized zone interlock setting
8
No
Yes
—
—
—
—
—
—
—
—
—
—
—
—
—
Pre-heating extension time setting
9
0 minutes
30 minutes
60 minutes
90 minutes
—
—
—
—
—
—
—
—
—
—
—
CO
2
sensor sharing setting
★
3
★
5
13
No
Yes
—
—
—
—
—
—
—
—
—
—
—
—
—
Humidity sensor sharing setting
(RA/OA)
★
5
★
9
14
No/No
Yes/No
No/Yes
Yes/Yes
—
—
—
—
—
—
—
—
—
—
—
External input setting (between J2-JC)
★
2
18(28)
0
Last command
Priority on
external input
Priority on
operation
Forced
OFF
—
24 hours
Ventilation
—
—
—
—
—
—
—
—
—
Power ON setting
1
OFF
ON
—
—
—
—
—
—
—
—
—
—
—
—
—
Power failure recovery setting
2
OFF
ON
—
—
—
—
—
—
—
—
—
—
—
—
—
External contact output changeover (X1-X2)
3
—
—
Damper
Output
—
Abnormal
output
Filter sign
—
—
—
—
—
—
—
—
—
CO
2
concentration control table setting
★
3
6
Linear
—
Notch A
Notch B
—
—
—
—
—
—
—
—
—
—
—
Fresh-up supply/exhaust setting
7
Supply air
Exhaust air
—
—
—
—
—
—
—
—
—
—
—
—
—
External input terminal function setting
(between J1-JC)
★
4
8
Fresh-up
Batch alarm
Batch error
Forced
OFF
Fan forced
OFF
More
airflow
—
—
—
—
—
—
—
—
—
Adapter for wiring output changeover
selection (Between X3-X4)
★
12
9
Humidification
output
(ordinary
humidification)
Abnormal
output
Fan
operation
(Ultra high/
High/Low)
Fan
operation
(Ultra high/
High)
Fan
operation
(Ultra high)
Fan
operation
(Ultra high/
High/Low)
Fan
operation
(Ultra high/
High/Low)
—
—
—
—
—
—
—
—
Adapter for wiring output changeover
selection (Between X1-X2)
★
12
9
Normal
operation
Normal
operation
Normal
operation
Normal
operation
Normal
operation
24-hour
ventilation
operation
and normal
operation
24-hour
ventilation
operation
—
—
—
—
—
—
—
—
External contact output changeover (X3-X4)
11
Damper output
Abnormal
output
Filter sign
Normal
operation
—
—
—
—
—
—
—
—
—
—
—
Auto cut-off control
★
10
12
Temperature
judgment
(exceeding 12
hours)
Temperature
judgment
(8~12hours)
Temperature
judgment
(below 8
hours)
—
—
—
—
—
—
OFF
Humidity
judgment
★
11
—
—
—
—
Intermittent weak notch operation setting
19(29)
1
OFF
Ventilation
rate
Ventilation
rate
Ventilation
rate
Ventilation
rate
Ventilation
rate
Ventilation
rate
—
—
—
—
—
—
—
—
(
1/15
Fan OFF
for 28 mins
Fan ON
for 2 mins
) (
1/10
Fan OFF
for 27 mins
Fan ON
for 3 mins
)(
1/6
Fan OFF
for 25 mins
Fan ON
for 5 mins
)(
1/4
Fan OFF
for 22.5 mins
Fan ON
for 7.5 mins
)(
1/3
Fan OFF
for 20 mins
Fan ON
for 10 mins
)(
1/2
Fan OFF
for 15 mins
Fan ON
for 15 mins
)
24-hour ventilation operation setting
★
13
4
OFF
Ventilation
rate
Ventilation
rate
Ventilation
rate
Ventilation
rate
Ventilation
rate
Ventilation
rate
Ventilation
rate
—
—
—
—
—
—
—
(
1/15
Fan OFF
for 28 mins
Fan ON
for 2 mins
) (
1/10
Fan OFF
for 27 mins
Fan ON
for 3 mins
)(
1/6
Fan OFF
for 25 mins
Fan ON
for 5 mins
)(
1/4
Fan OFF
for 22.5 mins
Fan ON
for 7.5 mins
)(
1/3
Fan OFF
for 20 mins
Fan ON
for 10 mins
)(
1/2
Fan OFF
for 15 mins
Fan ON
for 15 mins
)
1/1
(Continuous
operation)
Reference CO
2
concentration shift
★
3
★
6
7
No shift
+200
+400
+600
-200
-400
-600
—
—
—
—
—
—
—
—
Setting to allow fan stop
★
3
★
7
8
Allowed
Prohibited
Allowed
Prohibited
—
—
—
—
—
—
—
—
—
—
—
Heater control kit setting
8
—
—
Heater
operation
Heater
operation
—
—
—
—
—
—
—
—
—
—
—
Bypass mode air volume setting
★
3
★
8
9
Ultra high
High
—
—
No fixed
volume
—
—
—
—
—
—
—
—
—
—
Ventilation mode changeover
control setting
★
9
12
Energy
efficient
ventilation
Comfort
ventilation
—
—
—
—
—
—
—
—
—
—
—
—
—
Bypass mode air volume
increase setting
★
8
14
No increase
More airflow
Ultra high
High
—
—
—
—
—
—
—
—
—
—
—
Fresh-up (Pre Vent) operation
ON/OFF setting
1A
—
OFF
ON
—
—
—
—
—
—
—
—
—
—
—
—
—
Forced fan ON
43
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Unit No. replacement
45
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Summary of Contents for VAM Series
Page 2: ......
Page 4: ...EDMMT712101 2 Table of Contents 17 6 Precautions for Design and Installation 181 ...
Page 56: ...Control System EDMMT712101 54 VAM HVE HVLT Series C 3P343420 1E ...
Page 138: ...Installation Manual EDMMT712101 136 VAM HVE HVLT Series 3P607378 3C ...
Page 139: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 137 3P607378 3C ...
Page 141: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 139 C EM20A032 ...
Page 142: ...Installation Manual EDMMT712101 140 VAM HVE HVLT Series C EM20A032 ...
Page 143: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 141 C EM20A032 ...
Page 147: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 145 3P607378 3C ...
Page 148: ...Details of Optional Accessories EDMMT712101 146 VAM HVE HVLT Series 3P607378 3C ...
Page 149: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 147 3P607378 3C ...
Page 150: ...Details of Optional Accessories EDMMT712101 148 VAM HVE HVLT Series 3P607378 3C ...
Page 151: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 149 3P607378 3C ...
Page 152: ...Details of Optional Accessories EDMMT712101 150 VAM HVE HVLT Series 3P607378 3C ...
Page 155: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 153 4P457318 1D ...
Page 156: ...Details of Optional Accessories EDMMT712101 154 VAM HVE HVLT Series 4P457318 1D ...
Page 157: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 155 4P457318 1D ...
Page 158: ...Details of Optional Accessories EDMMT712101 156 VAM HVE HVLT Series 4P457318 1D ...
Page 159: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 157 4P457318 1D ...
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......