Control System
EDMMT712101
28
VAM-HVE/HVLT Series
Contr
ol
method
Air conditioner interlock system (commercial multi air conditioners (building multi) /SkyAir)
1 group interlocking control
(standard system)
1 group interlocking control
(duct direct connection system)
Interlocking control of 2 or more groups
Purpose • Application
Perform energy-saving interlocked control
of Heat Reclaim Ventilator Unit using the
remote controller for commercial multi air
conditioners (building multi) /SkyAir.
During intermediate periods, independent
operation of Heat Reclaim Ventilator Unit
is possible with a remote controller for air
conditioner.
Energy-saving interlocked control by duct
connection of Heat Reclaim Ventilator Unit and
indoor unit of commercial multi air conditioners
(building multi) /SkyAir within the same group.
※
This is available only during interlock using
remote controller lines.
Perform energy-saving interlocked control of 2 or more
groups of Heat Reclaim Ventilator Unit and indoor unit
of commercial multi air conditioners (building multi) /
SkyAir.
Heat Reclaim Ventilator Unit operates if any of the
indoor units starts operation.
During intermediate periods, independent operation
of Heat Reclaim Ventilator Unit is also possible with a
remote controller for air conditioner.
System overview
Heat Reclaim
Ventilator Unit
Remote controller
Indoor unit
Indoor unit
Heat Reclaim
Ventilator Unit
Remote controller
Duct
Centralized transmission line
Wiring adapter
for electrical
appendices
Heat Reclaim
Ventilator Unit
Indoor
unit
Indoor
unit
Remote
controller
Remote
controller
Remote
controller
Indoor unit
Essential optional
accessory
_____________________
_____________________
█
Wiring adapter for electrical appendices
KRP2A Series (use the applicable models)
〔
One adapter connection is provided to the
centralized transmission line. Adapter can also
be connected to the air conditioner.
〕
Functions
Energy-saving interlocked operation is performed by operating the remote controller for
indoor unit of commercial multi air conditioners (building multi) /SkyAir.
Ventilation mode and rate can be switched for BRC1H62, BRC1E63.
Other settings are made in the field setting mode.
Energy-saving interlocked operation of Heat Reclaim
Ventilator Unit is performed if any of the indoor units on
the same centralized transmission line starts operation.
※
All air conditioners in the system will be interlocked.
Be careful if there are many separate groups.
Number of units controlled
• Wiring length
Up to 16 units of a combination of Heat
Reclaim Ventilator Unit and indoor units
of commercial multi air conditioners
(building multi) /SkyAir under energy-saving
interlocking (within the same group)
Total remote controller wiring length: Up
to 500m
Up to 16 units of a combination of Heat
Reclaim Ventilator Unit and indoor units
of commercial multi air conditioners
(building multi) /SkyAir under energy-saving
interlocking by duct direct connection (within
the same group)
Total remote controller wiring length: Up to
500m
The maximum total number of groups is 64 groups
Max. length of centralized transmission line: Up to
1000m
Notes
Add BRC1H62 to perform control
by 2 remote controllers.
Be sure to set duct direct connection to
“Yes”.
Heat Reclaim Ventilator Unit operates only
when the air conditioner fan is in operation
to prevent dust from falling from indoor unit
of commercial multi air conditioners (building
multi) /SkyAir. Therefore, independent
operation of Heat Reclaim Ventilator Unit is
not allowed during intermediate periods. Air
conditioner is used in fan operation.
24-hour operation setting and intermittent
weak notch operation are not available for
duct direct connection system.
Duct direct connection is not allowed
Set the zone interlock to “Yes”.
Page
32
33
34
Summary of Contents for VAM Series
Page 2: ......
Page 4: ...EDMMT712101 2 Table of Contents 17 6 Precautions for Design and Installation 181 ...
Page 56: ...Control System EDMMT712101 54 VAM HVE HVLT Series C 3P343420 1E ...
Page 138: ...Installation Manual EDMMT712101 136 VAM HVE HVLT Series 3P607378 3C ...
Page 139: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 137 3P607378 3C ...
Page 141: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 139 C EM20A032 ...
Page 142: ...Installation Manual EDMMT712101 140 VAM HVE HVLT Series C EM20A032 ...
Page 143: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 141 C EM20A032 ...
Page 147: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 145 3P607378 3C ...
Page 148: ...Details of Optional Accessories EDMMT712101 146 VAM HVE HVLT Series 3P607378 3C ...
Page 149: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 147 3P607378 3C ...
Page 150: ...Details of Optional Accessories EDMMT712101 148 VAM HVE HVLT Series 3P607378 3C ...
Page 151: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 149 3P607378 3C ...
Page 152: ...Details of Optional Accessories EDMMT712101 150 VAM HVE HVLT Series 3P607378 3C ...
Page 155: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 153 4P457318 1D ...
Page 156: ...Details of Optional Accessories EDMMT712101 154 VAM HVE HVLT Series 4P457318 1D ...
Page 157: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 155 4P457318 1D ...
Page 158: ...Details of Optional Accessories EDMMT712101 156 VAM HVE HVLT Series 4P457318 1D ...
Page 159: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 157 4P457318 1D ...
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......