EDMMT712101
Control System
VAM-HVE/HVLT Series
43
Distant control by external input
Purpose
•
Functions
Heat Reclaim Ventilator Unit can be started/stopped remotely by non-voltage constant a contact signal.
POINT
During group control, Heat Reclaim Ventilator Unit starts/stops together with the entire group if it is connected to any one of the units in
the group.
Example of control wiring
J2
JC
P1 P2
P1 P2
Transmission wiring is up to 50m.
(Contact on site)
Heat Reclaim Ventilator Unit
Remote controller
Specifications for external contact
• Non-voltage normally open contact
• Microcurrent contact (Minimum applicable load: DC12V, 1mA or below)
Switch number that needs to be changed for the system
Field settings using remote controller is required.
Field settings using remote controller
Mode
No.
Setting switch
No.
Setting position
01
02
03
04
External input setting
(between J2 - JC)
18 (28)
0
Last command
Priority on external
input
Priority on operation
Forced OFF
Factory default setting
Details of external input setting
Setting position
Control details
01
Last command
Only during independent operation of Heat Reclaim Ventilator Unit.
External input is not allowed when interlocked with air conditioner.
02
Priority on external
input
Remote controller is prohibited when the unit is “started” by an external input. Remote controller is allowed
when the unit is “stopped” by external input.
External input is not allowed when interlocked with air conditioner.
03
Priority on operation
The unit operates when either the remote controller for the air conditioner or external input is set to “start”
when interlocked with air conditioner.
This setting can be made only during interlock with air conditioner.
04
Forced OFF
Operation stops at the time of non-voltage normally open contact input by external input. (No automatic
recovery)
Essential optional accessory
NIL.
Summary of Contents for VAM Series
Page 2: ......
Page 4: ...EDMMT712101 2 Table of Contents 17 6 Precautions for Design and Installation 181 ...
Page 56: ...Control System EDMMT712101 54 VAM HVE HVLT Series C 3P343420 1E ...
Page 138: ...Installation Manual EDMMT712101 136 VAM HVE HVLT Series 3P607378 3C ...
Page 139: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 137 3P607378 3C ...
Page 141: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 139 C EM20A032 ...
Page 142: ...Installation Manual EDMMT712101 140 VAM HVE HVLT Series C EM20A032 ...
Page 143: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 141 C EM20A032 ...
Page 147: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 145 3P607378 3C ...
Page 148: ...Details of Optional Accessories EDMMT712101 146 VAM HVE HVLT Series 3P607378 3C ...
Page 149: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 147 3P607378 3C ...
Page 150: ...Details of Optional Accessories EDMMT712101 148 VAM HVE HVLT Series 3P607378 3C ...
Page 151: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 149 3P607378 3C ...
Page 152: ...Details of Optional Accessories EDMMT712101 150 VAM HVE HVLT Series 3P607378 3C ...
Page 155: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 153 4P457318 1D ...
Page 156: ...Details of Optional Accessories EDMMT712101 154 VAM HVE HVLT Series 4P457318 1D ...
Page 157: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 155 4P457318 1D ...
Page 158: ...Details of Optional Accessories EDMMT712101 156 VAM HVE HVLT Series 4P457318 1D ...
Page 159: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 157 4P457318 1D ...
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......