Control System
EDMMT712101
66
VAM-HVE/HVLT Series
Usage conditions
[General information]
z
Do not install in the following locations or areas.
• Places that are prone to fogs (the moisture resistant type can
be used within the range of [
①
Ambient conditions])
p0LACESEXPOSEDTOHIGHTEMPERATURESORDIRECTÛAMES
• Places with a large amount of oily smoke such as cooking
rooms
• Places such as mechanical and chemical factories where
the return air (RA), outside air (OA) or air at the installation
site generates harmful gases such as acids, alkalis, organic
solvents, paints and pesticides, as well as gases that contain
corrosive components.
• Places with high temperature and humidity such as
a bathroom, heated pool, mushroom cultivation room, bedrock
bath (the moisture resistant type can be used within the range
of
[
①
Ambient conditions])
• Places where damages due to salt, hot spring or the like occur
p0LACESTHATGOBELOWFREEZINGPOINTFORTHEHUMIDIÚCATIONTYPE
and outside air processing type)
• Places with machines that generate electromagnetic waves
p0LACESWHEREÛAMMABLEGASMAYLEAKPLACESWHERECARBONÚBER
ORÛAMMABLEDUSTISPRESENTINTHEAIRANDPLACESWHEREVOLATILE
ÛAMMABLEMATERIALSSUCHASTHINNERANDGASOLINEAREHANDLED
• Places where oil is present in the air, oil is scattered, or a large
amount of steam is present
• Places that hair sprays are frequently used such as barbers and
beauty salons
• Places with a large amount of smoke such as smoking areas
p0LACESWITHFREQUENTVOLTAGEÛUCTUATIONSSUCHASFACTORIES
• Installation on vehicles and ships
z
Do not use the product to collect the heat of odorous air and supply it to other places.
z
$ONOTALLOWTHEAIRFROMTHEEXHAUSTSIDEOUTLETORANAIRCONDITIONERTODIRECTLYÛOWINTOTHEOUTSIDEAIRSUCTIONPORTLOCATEDOUTDOORS
z
Install the outside air intake port in the outdoors where it does not intake exhaust gas or factory smoke that causes bad odors or
OXYGENDEÚCIENCYINTHEROOM
z
Protection against insect invasion
In suburban buildings where there are windows or outdoor lights near the outside air suction port (OA), and places where insects
GATHERAROUNDTHEILLUMINATIONLIGHTSMALLINSECTSMAYENTERTHEOUTSIDEAIRSUCTIONPORT/! PASSTHROUGHTHEAIRÚLTERANDINVADE
the room. Also, small insects that entered from the outside air suction port (OA) may come out from the exhaust air outlet (EA).
"ESURETOPROVIDEINSECTINVASIONMEASURESSUCHASAÚLTERBOXPREPAREDLOCALLY DURINGTHEDESIGNPROCESS
z
In cold regions or places with strong outside wind, outdoor wind may enter through the duct while the unit is stopped.
Be sure to install an electric shutter or the like to prevent this. If water is accumulated in the unit, wipe it off before use.
z
The unit cannot be driven in cold regions and the like that are out of the operating conditions temporarily or throughout the day.
Stop the operation if the installed environment is out of the operating condition range.
z
Intake of fog, haze or high-humidity air may cause water leakage to the outside of the unit due to water droplets dripping from
THEAIRÚLTERORHEATEXCHANGEELEMENTORDAMAGETOELECTRICALPARTSSUCHASDAMPERMOTORS3TOPTHEOPERATIONINSUCHACASE
If water is accumulated in the unit, wipe it off before use.
z
When using the unit in cold regions, there is a risk of condensation and freezing, so be sure to check the operating conditions and
precautions, and provide additional heat insulating materials. Stop the operation at -15°C or less.
z
If the ambient temperature of the Heat Reclaim Ventilator unit exceeds the upper limit of the operating range (due to a heater for
heating supply air installed near the product, etc.), a damage or malfunction may occur. Make sure that the ambient temperature and
the outside air / return air temperature do not exceed the upper limit of the operating range.
z
Do not install the unit in a place that's exposed to ultraviolet rays, as it will cause the heat insulating material to deteriorate.
z
In areas affected by volcanic ash, be sure to
INSTALLAREMOVALDEVICESUCHASAÚLTERBOX
(prepared locally) at the outside air intake port
and indoor exhaust port.
z
Salt damage measures in coastal areas
If the Heat Reclaim Ventilator unit is installed
INABUILDINGINACOASTALAREAANDMEASURESAGAINSTSALTDAMAGEARECONSIDEREDNECESSARYCONNECTAÚLTERFORCOLLECTINGSEASALT
PARTICLESÚLTERFORPREVENTINGSALTDAMAGE TOTHEOUTSIDEAIRSUCTIONPORT/! USINGDUCTS
z
Where the outside air or exhaust suction air exceeds 40°C, the life of the unit may be
SHORTENEDDUETODEFORMATIONOFRESINPARTSSUCHASAIRÚLTERSORDETERIORATIONOFINSULATION
of electrical parts such as motors.
z
When the indoor pressure is negative or the outside wind is strong, the unit may take in the
OUTSIDEAIREVENWHILESTOPPED)NSUCHACASEINSTALLELECTRICSHUTTERSÚELDSUPPLIED ORTHE
like for each of the outside air suction port (OA) and exhaust air outlet (EA) as a wind
intrusion prevention measure.
SA
RA
Heat Reclaim
Ventilator unit
Filter for prevention of salt damage
Please use filter more than MERV14 Grade to
prevent salt damage
OA
EA
SA
RA
Heat Reclaim
Ventilator unit
Electric shutter (field supplied)
OA
EA
Summary of Contents for VAM Series
Page 2: ......
Page 4: ...EDMMT712101 2 Table of Contents 17 6 Precautions for Design and Installation 181 ...
Page 56: ...Control System EDMMT712101 54 VAM HVE HVLT Series C 3P343420 1E ...
Page 138: ...Installation Manual EDMMT712101 136 VAM HVE HVLT Series 3P607378 3C ...
Page 139: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 137 3P607378 3C ...
Page 141: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 139 C EM20A032 ...
Page 142: ...Installation Manual EDMMT712101 140 VAM HVE HVLT Series C EM20A032 ...
Page 143: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 141 C EM20A032 ...
Page 147: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 145 3P607378 3C ...
Page 148: ...Details of Optional Accessories EDMMT712101 146 VAM HVE HVLT Series 3P607378 3C ...
Page 149: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 147 3P607378 3C ...
Page 150: ...Details of Optional Accessories EDMMT712101 148 VAM HVE HVLT Series 3P607378 3C ...
Page 151: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 149 3P607378 3C ...
Page 152: ...Details of Optional Accessories EDMMT712101 150 VAM HVE HVLT Series 3P607378 3C ...
Page 155: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 153 4P457318 1D ...
Page 156: ...Details of Optional Accessories EDMMT712101 154 VAM HVE HVLT Series 4P457318 1D ...
Page 157: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 155 4P457318 1D ...
Page 158: ...Details of Optional Accessories EDMMT712101 156 VAM HVE HVLT Series 4P457318 1D ...
Page 159: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 157 4P457318 1D ...
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......