Specification
EDMMT712101
82
VAM-HVE/HVLT Series
Note:
Refer to page 85.
(60 Hz)
Model
VAM150HVLT
VAM250HVLT
VAM350HVLT
Power supply
Single phase, 220 V, 60 Hz
Airflow Rate
Ultra-High m³ / h
150
250
350
High
m³ / h
150
250
350
Low
m³ / h
80
145
235
External static pressure
Ultra-High
Pa
155
135
230
High
Pa
100
60
80
Low
Pa
28
20
36
Temperature
exchange
efficiency
Average
Ultra-High
%
71.5
68.5
72.5
High
%
71.5
68.5
72.5
Low
%
74.5
72.5
76.0
Cooling
Ultra-High
%
66.0
60.5
65.0
High
%
66.0
60.5
65.0
Low
%
69.5
65.5
70.0
Heating
Ultra-High
%
77.0
76.5
79.5
High
%
77.0
76.5
79.5
Low
%
79.0
79.0
82.0
Enthalpy
exchange
efficiency
Cooling
Ultra-High
%
63.5
60.0
62.5
High
%
63.5
60.0
62.5
Low
%
66.5
62.0
65.0
Heating
Ultra-High
%
71.5
69.5
72.0
High
%
71.5
69.5
72.0
Low
%
77.0
73.5
75.0
Operating sound
Heat exchange mode
Ultra-High
dBA
34.0
33.5
34.5
High
dBA
28.0
28.0
27.5
Low
dBA
20.0
21.0
22.0
Bypass mode
Ultra-High
dBA
36.0
34.5
34.5
High
dBA
28.5
29.0
27.5
Low
dBA
20.5
21.5
23.0
Normal input
Heat exchange mode
Ultra-High
W
132
172
231
High
W
118
144
207
Low
W
67
79
145
Normal input at 0 Pa external static pressure
Ultra-High
W
156
192
278
Normal amp.
Heat exchange mode
Ultra-High
A
0.61
0.81
10.6
High
A
0.55
0.66
0.95
Low
A
0.32
0.37
0.68
Effective ventilation rate
Ultra-High
%
90
90
90
Dimensions
H × W × D
mm
278 × 551 × 810
278 × 551 × 810
306 × 800 × 879
Weight
kg
22
22
31
Connection duct
diameter
Indoor side
mm
100
150
150
Outdoor side
mm
100
150
150
Unit ambient
condition
Around the unit
–10°C to 50°CDB (80% RH or less)
Outdoor air
–15°C to 50°CDB (80% RH or less)
Return air
–10°C to 50°CDB (80% RH or less)
Drawing number
3D135416B
3D135416B
3D135416B
Summary of Contents for VAM Series
Page 2: ......
Page 4: ...EDMMT712101 2 Table of Contents 17 6 Precautions for Design and Installation 181 ...
Page 56: ...Control System EDMMT712101 54 VAM HVE HVLT Series C 3P343420 1E ...
Page 138: ...Installation Manual EDMMT712101 136 VAM HVE HVLT Series 3P607378 3C ...
Page 139: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 137 3P607378 3C ...
Page 141: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 139 C EM20A032 ...
Page 142: ...Installation Manual EDMMT712101 140 VAM HVE HVLT Series C EM20A032 ...
Page 143: ...EDMMT712101 Installation Manual VAM HVE HVLT Series 141 C EM20A032 ...
Page 147: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 145 3P607378 3C ...
Page 148: ...Details of Optional Accessories EDMMT712101 146 VAM HVE HVLT Series 3P607378 3C ...
Page 149: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 147 3P607378 3C ...
Page 150: ...Details of Optional Accessories EDMMT712101 148 VAM HVE HVLT Series 3P607378 3C ...
Page 151: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 149 3P607378 3C ...
Page 152: ...Details of Optional Accessories EDMMT712101 150 VAM HVE HVLT Series 3P607378 3C ...
Page 155: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 153 4P457318 1D ...
Page 156: ...Details of Optional Accessories EDMMT712101 154 VAM HVE HVLT Series 4P457318 1D ...
Page 157: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 155 4P457318 1D ...
Page 158: ...Details of Optional Accessories EDMMT712101 156 VAM HVE HVLT Series 4P457318 1D ...
Page 159: ...EDMMT712101 Details of Optional Accessories VAM HVE HVLT Series 157 4P457318 1D ...
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......