STAND-ALONE NIGHTTIME FREE COOLING 
OPERATION

OFF

ON

22:00

24:00

40

30

20

OFF

Outdoor 
temperature

Indoor 
temperature

Set temperature

Nighttime free cooling operation

Following morning 
(time)

T

emper

ature

T

otal heat 

e

xchanger

This is performed for independent systems and 
centralized systems.
Temperature to be set can be selected by making fi eld 
settings.

<

Unit operation

>

The total heat exchanger unit compares the indoor 
and outdoor temperatures after it stops for the night. 
If the following conditions are met, the operation 
starts and when the indoor temperature reaches the 
temperature setting of the total heat exchanger unit, 
the operation stops.

Conditions;

1. The indoor temperature is higher than the 

temperature setting of the total heat exchanger unit.

2. The outdoor temperature is lower than the indoor 

temperature.

If the above conditions are not met, reevaluation is 
made every 60 minutes.

•  For other functions, see the operation manual of the 

remote control.

4  MAINTENANCE 

(for a qualified service person only)

WARNING

•  Do not use flammable gas (such as hair spray 

and insecticide) near the main unit. Do not wipe 
the main unit and remote control with thinner, 
etc.

This may cause cracks, electric shock, or ignition.

•  Do not wash the total heat exchanger unit with 

water (not including air filters).

If the electrical parts or motors get wet with water, 
it may cause electric leakage, resulting in electric 
shock or fire.

•  Be sure to stop the operation, and turn the 

breaker off before cleaning or inspection.

As the fan inside the unit is rotating at high speed, it 
will cause electric shock or injury.

CAUTION

•  Use gloves when cleaning.

Cleaning without gloves may cause injury.

•  Watch your step when working in high places.

If the scaffold is unstable, you may fall or topple 
down thus causing injury.

NOTE 

•  Do not operate the unit without air filter except 

during cleaning.
Missing air filter causes clogged heat exchange 
element which may lower operation efficiency and 
cause a failure.

•  When cleaning, replace heat exchange element 

if its’ knob is found damaged or in deteriorating 
condition as it is a potential dropping hazard.

•  Do not install anything (such as kitchen paper) 

other than the genuine air filters on the air inlet.
Doing so may lower operation efficiency and cause 
freezing or leakage.

•  Cleaning of air filter or heat exchange element, 

installation and replacement high-performance filter 
(optional accessory) involves a work in high places 
and it is dangerous.
Be sure to ask your dealer to have such works 
done.

•  If water is in the unit, clean it by wiping it off with a 

soft cloth.

1-OM-VAM-HVE-DAIKIN-EN.indd   5

1-OM-VAM-HVE-DAIKIN-EN.indd   5

23/9/2021   2:29:06 PM

23/9/2021   2:29:06 PM

Summary of Contents for VAM150HVE

Page 1: ...0HVE VAM250HVE VAM350HVE VAM500HVE VAM650HVE VAM800HVE VAM1000HVE VAM1500HVE VAM2000HVE Total Heat Exchanger Heat Reclaim Ventilator For Production only For Indonesia For Thailand For Vietnam 3P645002...

Page 2: ...CVR OM VAM HVE DAIKIN EN indd 2 CVR OM VAM HVE DAIKIN EN indd 2 23 9 2021 5 08 50 PM 23 9 2021 5 08 50 PM...

Page 3: ...any problems or there is a malfunction please refer to this operation manual Please keep this manual for your future reference whenever you do not understand how to use it when something is wrong with...

Page 4: ...exchange element may be noticeable it is not harmful The smell will gradually go away as the unit is used It exchanges the indoor heat with the outdoor air conditioning the outdoor air closer to the a...

Page 5: ...s Connection chamber Damper 2 pcs Air supply fan 2 pcs Air filter 4 pcs Remote control optional accessory Electrical component box Name plate Heat exchange elements 4 pcs Open and close it when cleani...

Page 6: ...eat Reclaim Ventilator unit Centralized controller Remote controller for Heat Reclaim Ventilator unit BRC1H62W K Remote controller for indoor unit Heat Reclaim Ventilator unit Combined operation syste...

Page 7: ...4 MODELS VAM150HVE VAM1000HVE MODELS VAM1500HVE VAM2000HVE Air filter Air filter 5 6 7 8 1 OM VAM HVE DAIKIN EN indd 5 1 OM VAM HVE DAIKIN EN indd 5 23 9 2021 2 29 05 PM 23 9 2021 2 29 05 PM...

Page 8: ...r dealer Young children should be supervised to ensure that they do not play with the appliances It may make your health worse by wrong operation Do not use heating appliances nearby the Heat Reclaim...

Page 9: ...one earth Incomplete earth may cause electrical shock or fire A high surge current from lightning or other sources may cause damage to the air conditioner Be sure to install an earth leakage breaker F...

Page 10: ...intenance space for the air filters the heat exchange elements and control box 16 RA Return air from room 17 SA Supply air to room 2 2 VENTILATION OPERATION See the operation manual of the remote cont...

Page 11: ...rature is higher than the temperature setting of the air conditioner combined 2 The outdoor temperature is lower than the indoor temperature If the above conditions are not met reevaluation is made ev...

Page 12: ...at exchanger unit with water not including air filters If the electrical parts or motors get wet with water it may cause electric leakage resulting in electric shock or fire Be sure to stop the operat...

Page 13: ...durability Do not wash the air filter with hot water of more than 50 C This may cause discoloration or deformation Do not expose the air filter to fire This may result in burning Do not expose the ai...

Page 14: ...all the maintenance cover 4 1 3 HOW TO INSTALL AND REPLACE THE HIGH PERFORMANCE FILTER OPTIONAL ACCESSORY Replace the high performance filter at least once a year Increase the frequency of replacement...

Page 15: ...ror code Usage under that status will lead to insufficient ventilation The air supply and exhaust fans should be checked once every one or two months You can make a simple check such as below way To c...

Page 16: ...the unit presents abnormal conditions burnt smell etc stop the operation and turn the breaker off Continued operation under such circumstances may result in a failure electric shock or fire Contact y...

Page 17: ...ore than 6 times hour for normal use Operation of the product is assumed to be 10 hours day 2500 hours year Table 1 Inspection Cycle and Maintenance Cycle Lists Name of Main Part Inspection Cycle Main...

Page 18: ...for appropriate maintenance design budgeting parts replacement cost etc If the unit is used for a building for The Building Sanitation Act Former Buiding Managment Act periodic inspection is required...

Page 19: ...CVR OM VAM HVE DAIKIN EN indd 3 CVR OM VAM HVE DAIKIN EN indd 3 23 9 2021 5 08 50 PM 23 9 2021 5 08 50 PM...

Page 20: ...Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global Lot 60334 Persiaran Bukit Rahman Putra 3 Taman Perindustrian Bukit Rahman Putra 47000 Sungai Buloh Selangor Darul Ehsan Mal...

Reviews: