Operation
Si71-812
14
Operation
Recommended Systems
1. System with a remote sensor connected to each indoor unit
On the ceiling chamber system with which generated heat loads are treated in the ceiling space, the suction
thermistor (body thermistor) mounted to the indoor unit alone cannot ensure the detection of room temperatures.
Consequently, for the indoor unit, in order to ensure the detection of the room temperatures, it is recommended to
change to the remote sensor system.
2. Connection of refrigerant piping
For the connection of refrigerant piping on the ceiling chamber system, it is recommended to provide a system
preventing the cool-heat changeover while in automatic mode on the VKM through connecting a base indoor unit in
the same duct system and the VKM to the same BS unit to interlock between the VKM and the indoor unit (*).
*
In order to interlock between the VKM and the indoor unit, the group control of remote controllers should be
provided.
Fig. 1 When interlocking between the base indoor unit and the VKM:
(Connect multiple indoor units and VKM to a single BS unit.)
Fig. 2 When connecting a single indoor unit or a single VKM to a single BS unit:
(If this is the case, use the VKM in fixed cooling or heating mode.)
3. Measures against inadequate humidification
When operating the system at a temperature in the ceiling space set higher than the initial setting, the heating
thermostat on the VKM may turn OFF to disable humidification. In this case, according to the field setting on the
remote controller, raise the heating set temperature. For details, refer to information on page 85.
Heat
Recovery
Indoor unit
Indoor unit
Indoor unit
In ceiling space
(ceiling chamber)
VKM
Remote
sensor
Remote
sensor
Remote
sensor
Air conditioner
remote controller
Air conditioner
remote controller
Air conditioner
remote controller
BS
BS
BS
Indoor
unit
VKM
remote controller A remote controller B
BS
BS
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...