Si71-812
Operation
Opration
19
1.4.3 Caution when Connecting the Indoor Unit Directly to the Duct
Follow the indications described below
a) When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as
with the outdoor unit, perform group-linked operation, and make the direct duct connection settings
from the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Refer to
15.10.1 concerning setting method.
b) Do not connect to the outlet side of the indoor unit. Depending on the fan strength and static pressure,
the unit might back up.
c) When it is connected to the suction side of indoor unit as a direct duct connection system, etc., since
there is a possibility that the body thermo of the indoor unit detects erroneously SA discharge from this
unit as indoor air, use the remote sensor (Optional).
EA
OA
RA
SA
Suction
grille